North American Wiring Practice
Drive
Connection
Gnd
Connection
Fig. 3.14 Sensor Cable Connections at the Transmitter (North American Wiring Practice)
3.3.3 MagMaster-CalMaster Adapter
When a MagMaster Transmitter is fitted with an adaptor board for use with a CalMaster Verification
Unit, wiring from the sensor to this adaptor board is shown in the following diagram.
To wire the adaptor plug, carefully pull off the plug from the adaptor board, connect the wires, using
only a screwdriver with a 2.5mm blade to tighten the terminal screws, and replace the plug.
Adaptor Plug
Red
(CD 1)
Yellow
(CD 2)
Yellow
Red
Ground Wire
Fig 3.15 Fitting the Sensor Wiring onto the Adaptor
3 ELECTRICAL INSTALLATION...
White Coax
Blue Inner (SIG 1)
Screen (DS 1)
Black Coax
Inner (SIG 2)
Screen (DS 2)
Black (SIG GND)
Cable Screen Connections
Drain Wire (ESCRN)
Pink
Caution. Remove any exposed
Grey
black conductive layer from the
inner insulation of both coaxial
Blue
cables
White
Violet
Sensor Cable
Signal
Connection