10. Specifications
Model
Nominal voltage and
input range
Nominal input frequency
and tolerance
Nominal output voltage:
Nominal output frequency 50/60 Hz (50Hz ±2% /
Output voltage regulation
in line mode
Output voltage regulation
in battery mode
Nominal output power
in W / VA
Output voltage waveform
Maximum output current
@ P . F.
Maximum output P .F.
Efficiency with nominal
load
Efficiency at rated load
Maximum operating
altitude at 100% of
nominal power
Online overload capability
Overload capacity in
battery mode
Current limitation:
Autonomy time at full
load
Battery recharge time
Transfer time
Outlets
Maximum input current
Specifications are subject to change without further notice.
SMART600PSGLCD
SMART1000PSGLCD
120V~, 97-145V
120V~, 97-145V
50/60 Hz (Frequency
50/60 Hz (Frequency
low/comeback:
low/comeback:
45/47Hz±0.2Hz;
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
Frequency high/
comeback:
comeback:
55/53Hz±0.2Hz;
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
65/63Hz±0.2Hz)
120V~ in line mode and
120V~ in line mode and
120V~ battery
120V~ battery
50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
60Hz ±1.67%)
120V~ (±10%)
120V~ (±10%)
120V~ (±10%)
120V~ (±10%)
360W / 600VA
600W / 1000VA
Sinusoidal in line mode
Sinusoidal in line mode
and Sinusoidal in battery
and Sinusoidal in battery
mode
mode
5A @ 120V~
8.3A @ 120V~
P .F. = 0.6
≥96%
≥96%
≥96%
≥96%
9842 ft. (3000 m)
9842 ft. (3000 m)
110%+15%/-5% for 5
110%+15%/-5% for 5
minutes; 120%+15%/-
minutes; 120%+15%/-
5% immediately and go
5% immediately and go
to fault
to fault
110%+15%/-5% for 10
110%+15%/-5% for 10
seconds; 120%+15%/-5%
seconds; 120%+15%/-5%
Shutdown immediately
Shutdown immediately
10A @ 120V~
10A @ 120V~
2.5 minutes @ 360W
2 minutes @ 600W
7 hours
7 hours
6ms Typical, 10ms Max
6ms Typical, 10ms Max
4x 5-15R outlets with
4x 5-15R outlets with
battery backup and surge;
battery backup and surge;
4x 5-15R outlets surge
4x 5-15R outlets surge
only
only
5A @ 120V~
8.3A @ 120V~
SMART1200PSGLCD
120V~, 97-145V
50/60 Hz (Frequency
low/comeback:
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
comeback:
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
120V~ in line mode and
120V~ battery
50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
120V~ (±10%)
120V~ (±10%)
720W / 1200VA
Sinusoidal in line mode
and Sinusoidal in battery
mode
10A @ 120V~
≥96%
≥96%
9842 ft. (3000 m)
110%+15%/-5% for 5
minutes; 120%+15%/-
5% immediately and go
to fault
110%+15%/-5% for 10
seconds; 120%+15%/-5%
Shutdown immediately
10A @ 120V~
2.5 minutes @ 720W
7 hours
6ms Typical, 10ms Max
5x 5-15R outlets with
battery backup and surge;
5x 5-15R outlets surge
only
10A @ 120V~
21
SMART1500PSGLCD
120V~, 97-145V
50/60 Hz (Frequency
low/comeback:
45/47Hz±0.2Hz;
or 55/57Hz±0.2Hz;
Frequency high/
comeback:
55/53Hz±0.2Hz;
65/63Hz±0.2Hz)
120V~ in line mode and
120V~ battery
50/60 Hz (50Hz ±2% /
60Hz ±1.67%)
120V~ (±10%)
120V~ (±10%)
900W / 1500VA
Sinusoidal in line mode
and Sinusoidal in battery
mode
12A @ 120V~
≥96%
≥96%
9842 ft. (3000 m)
110%+15%/-5% for 5
minutes; 120%+15%/-
5% immediately and go
to fault
110%+15%/-5% for 10
seconds; 120%+15%/-5%
Shutdown immediately
15A @ 120V~
3 minutes @ 900W
7 hours
6ms Typical, 10ms Max
5x 5-15R outlets with
battery backup and surge;
5x 5-15R outlets surge
only
12A @ 120V~