Only Modbus address 0001 can be accessed at all times. All other Modbus addresses
can only be accessed if the CAN communication between GCP-MG and GCP-30 has been
established. If this is not the case, Modbus exception code 0B Gateway target device
failed to respond is returned indicating the GCP-30 is not present on the CAN bus.
For the GCP-30 MUX data table, the GCP-MG acts as a transparent gateway between the
GCP-30 unit and the Modbus. Except for the device status register at Modbus address
0001, it does not perform any modification to the representation of the data values.
The Woodward "GCP-30 Series Genset Control" manual [GCP30] is the ultimate reference
for the encoding and representation of the data values. Please refer to the "Transmission
Telegram" table in Appendix C "Interface Control" of this manual for further details.
The following table shows the relationship between Modbus addresses and the so called
MUX identifiers or word numbers:
Block
Modbus
address
3
0001
3
0002
3
0003
3
0004
3
0005
3
0006
3
0007
3
0008
3
0009
3
0010
3
0011
3
0012
3
0013
3
0014
3
0015
3
0016
3
0017
3
0018
3
0019
3
0020
3
0021
3
0022
3
0023
3
0024
3
0025
3
0026
3
0027
3
0028
UMGCPMG-2201
GCP-30
GCP-30
GCP-30 manual designator
MUX
word no.
n/a
n/a
CAN device status register
Bit 1: 1 = CAN communication GCP-MG and GCP-30 OK
Bit 2-16: reserved for future use
0/1
1
Generator voltage delta V12
0/2
2
Generator frequency f
0/3
3
Actual generator real power P
1/1
4
Exponents
1/2
5
Real power set point value
1/3
6
Conversion factor steps to kW
2/1
7
Bus bar voltage delta V12
2/2
8
Mains voltage delta V12
2/3
9
Currently present alarm class
3/1
10
Control register 2
3/2
11
Actual mains interchange (import/export) real power
3/3
12
Control register 1
4/1
13
Alarm message IKD (SC06)
4/2
14
Internal alarm 6
4/3
15
Generator voltage delta V23
5/1
16
Generator voltage delta V31
5/2
17
Generator voltage delta V1N
5/3
18
Generator voltage delta V2N
6/1
19
Generator voltage delta V3N
6/2
20
Configuration [T1]-[T4]
6/3
21
Engine speed measured via the Pickup
7/1
22
Generator current in L1
7/2
23
Generator current in L2
7/3
24
Generator current in L3
8/1
25
Actual generator reactive power
8/2
26
Generator cos phi
8/3
27
Current reserve power in the system in kW
Modbus data reference
35