Remote control with the GCP-MG
Application Note 302
Revision 1.0, December 2008
Preparation ............................................................................................................................................. 1
GCP-30 setup .................................................................................................................................. 1
GCP-MG setup ................................................................................................................................ 1
Testing ................................................................................................................................................... 2
PLC program implementation .................................................................................................................... 5
References .............................................................................................................................................. 5
This Application Note describes how to perform remote control operations like genset start, stop and
alarm reset using Modbus and the GCP-MG gateway.
Preparation
All devices have to be configured first to a allow remote control as it is disabled by default. The
GCP-30 unit also requires some hardwiring.
GCP-30 setup
Before being able to use remote control, please check that the GCP-30 unit has been parameterized
accordingly. Refer to chapter Interface in your GCP-30 Series Genset Control manual.
• GCP-30 parameter 120
• Discrete input
Automatic 2
• GCP-30 parameter 122
edgment is required.
• GCP-30 must be in
Automatic
GCP-MG setup
Remote control needs to be enabled on the GCP-MG gateway for each device.
Use a web browser and point it to the IP address of your GCP-MG gateway. The overview page will
appear.
To configure the Modbus access, enter the
or
menu entry. This opens either the GCP-30 settings or the LS 4 settings.
LS 4
For each device you require remote control, set to either
below. Save the configuration settings.
AN302-0802
Control via COM X1X5
(terminal 5) must be asserted.
Ackn. F2,F3 via COM interf
mode (Automatic LED must be lit)
Configuration
must be turned on
must be turned on if remote alarm acknowl-
sub-menu and click on either the
or
control
monitored control
GCP-30
as shown
1