Figure 5.4: CAN communication status page
This page shows accumulated readings since the GCP-MG was last activated or
reset. If power to the GCP-MG is lost, all cumulative values are reset to zero.
The CAN communication channel between a GCP-30 or LS 4 unit and the GCP-MG can
be in one of the following states:
OK
The CAN communication channel with the GCP-30 or LS 4 unit has been established.
The GCP-30 or LS 4 control is cyclically updating data.
WAIT
The presence of a GCP-30 or LS 4 unit has been detected however the GCP-MG is
currently waiting to receive a complete data set. It takes approximately between
2.3 and 3 seconds to receive a full data set from the GCP-30 and approximately 10
seconds from the LS 4.
TIME-OUT
No CAN message was received for a period of 1 second. A GCP-30 control is supposed
to send a CAN message every 100 ms, a LS 4 every 200 ms.
The following statistics are maintained:
Messages received
A counter that increments each time an inbound CAN message matching the shown
CAN ID is successfully received.
Messages sent
A counter that is incremented each time a CAN message is sent. CAN messages are
only sent if Remote Control is enabled for this GCP-30 or LS 4.