Installation Guide Servo Drives
8 Calibrated Measuring Amplifier (C1250-MI-XC-xS-Cxx)
The drives with the ending -Cxx are specially designed for measuring applications. They come with a factory calibration
certificate for the analog inputs on X4. The analog inputs on X4 provide a measuring error of less than 1%.
It is the user's responsibility to allow a reasonable period for recalibration. We recommend a calibration interval of 12
months.
9 Description of the connectors / Interfaces
9.1
PE
PE
Protective Earth
•
PE
Use min. 4 mm
•
Tightening torque: 2 Nm (18 lbin)
9.2
X1
X1
Motor Supply
PWR
PGND
Connector has to be
Motor Supply: 72 VDC nominal, 24...85 VDC
ordered separately:
Absolute max. Rating: 72 VDC +20%.
see chapter 16
External Circuit Breaker: 15 A / min. 100 VDC / C-Trip / 5 kA rms SCCR
Ordering
* for cURus: External Fuse: 16A slow blow / min. 100VDC
Information)
If motor supply voltage exceeds 90 VDC, the drive will go into error state.
•
Use 60/75 °C copper conductors only
•
Conductor Cross-Section 2.5 mm
Page 10 / 29
2
(AWG11)
2
(AWG14) max Length 3 m
C1250-MI
ENG
NTI AG / LinMot