Base Terminal Definitions - Veesta World V-PM2000 Series User Manual

Enhanced ied, power measurement, power quality and monitoring device
Table of Contents

Advertisement

VP-2040 Enhanced IED
V-PM2000 Series, Veesta Power Measurement
Instructions & User's Manual
6.2.1

Base Terminal Definitions

No.
Code
1
L/+
2
--
3
N/-
4
--
5
FG
6
--
7
(Not Exist)
8
(Not Exist)
9
I32
10
I31
11
I22
12
I21
13
I12
14
I11
15
A+
16
B-
17
Sg
18
--
19
--
20
A1
(option)
21
Ag
(option)
22
VN
23
--
24
V3
25
--
26
V2
27
--
28
V1
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
In regarding the only base unit used, there are 2 rows terminal and
the terminal numbered from 1 up to 28. Please pay attention that
terminal with code (--) tagged as NC (Not Connect), so you should
leave this terminal float and disconnect to any wiring.
Table 6-1: VP-2040 Base Terminal Definitions
Definition
Positive of power supply
--
Negative of power supply
--
Earth protection Field Ground System
--
Phase C current outgoing line
Phase C current incoming line
Phase B current outgoing line
Phase B current incoming line
Phase A current outgoing line
Phase A current incoming line
Positive pole of RS485 (A)
Negative pole of RS485 (B)
Communication shielded earth of RS485
--
--
Positive pole analog output (If AO option selected)
Negative pole of Analog Output (If AO option selected)
Voltage neutral line
--
Phase C voltage
--
Phase B voltage
--
Phase A voltage