3.1.7

Data Logger Feature

1.
Event Logger
2.
Control Output
3.
Max / Min Logger
4.
Demand / Max Logger
3.1.8

Standards

1.
Metering
2.
Dielectric Strength
3.
Impulse & Surge Test
(EMC)
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
:
50 events with time-stamped in NVRAM
Status change of switch input
Activation of set-points
Alarms Operation of controlled relay output
:
2 assignable relay outputs
:
12 parameters without time-stamped A1, A2, A3,
W, Var, VA, Voltage V1,V2,V3 THD, Current
A1,A2,A3 THD
:
4 parameters with time-stamped AE, W, Var, VA
:
Class 1 For:
Electricity Metering Part 21 Active Energy
Electricity Metering Part 21 Reactive Energy
:
2KV ACrms 1 minute
Insulation resistance ≥50MΩ
:
Electrostatic discharge immunity test
Radiated immunity test
Electrical fast transient/burst immunity test
Surge immunity test (1, 2/50μs~8/20μs)
Conducted emissions
Radiated emissions
Chapter 3 - Specifications
IEC 62053-21
IEC 62053-23
IEC 255-5
IEC 61000-4-2,Level 4
IEC 61000-4-3,Level 3
IEC 61000-4-4,Level 4
IEC 61000-4-5,Level 3
EN 55022,Class B
EN 55022,Class B