Veesta World V-PM2000 Series User Manual

Enhanced ied, power measurement, power quality and monitoring device
Table of Contents

Advertisement

Quick Links

Veesta World Co
User's Manual
V-PM2000 Series
VP-2040 User's Manual
Enhanced IED, Power Measurement, Power Quality
and Monitoring Device
Author: Veesta World Co., Engineering Department

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the V-PM2000 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Veesta World V-PM2000 Series

  • Page 1 Veesta World Co User’s Manual V-PM2000 Series VP-2040 User’s Manual Enhanced IED, Power Measurement, Power Quality and Monitoring Device Author: Veesta World Co., Engineering Department...
  • Page 2 In no event shall Veesta World Co be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall Veesta World Co be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
  • Page 3 VP-2040 Enhanced IED Document History V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual DOCUMENT HISTORY Version Date Comment 2017/07/18 First issue 2019/08/18 Add CT information Page 3 of 100 All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
  • Page 4: Table Of Contents

    VP-2040 Enhanced IED Table of Content V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual TABLE OF CONTENT Chapter 1 - Introduction ..............9 General Information...............9 Features ................10 1.2.1 Characteristics ............10 1.2.2 Standard features ............11 1.2.3 Metering..............11 1.2.4 Set-points to Alarms..........12 1.2.5 Communications ............12...
  • Page 5 VP-2040 Enhanced IED Table of Content V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Demand Parameters ............24 Energy Parameters .............25 Harmonic Parameters ............26 Chapter 5 - IED Capability..............27 Status Input .................27 Relay Output ...............28 Pulse Output................30 Analog Output ..............32 Alarm System ..............34...
  • Page 6 VP-2040 Enhanced IED Table of Content V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 8.3.3 Data .................59 8.3.4 CRC .................59 8.3.5 Protocol..............59 Modbus Framing ..............60 8.4.1 Address Field............60 8.4.2 Function Field ............60 8.4.3 Data field..............60 8.4.4 Error Check filed ............61 8.4.5 Error Detection............61...
  • Page 7 VP-2040 Enhanced IED Table of Content V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual TABLE OF FIGURES Figure 1-1: VP-2040 E-IED Metering Conventions............13 Figure 2-1: VP-2040 Models & Ordering ..............16 Figure 4-1: VP-2040 Power Factor Symbols .............23 Figure 4-2: VP-2040 Power Factor Symbols .............24 Figure 5-1: VP-2040 Status Input Capability .............27...
  • Page 8 VP-2040 Enhanced IED Table of Content V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual INDEX OF TABELS Table 1-1: VP-2040 Set-points condition table ............12 Table 4-1: VP-2040 Electrical Parameters ..............22 Table 4-2: VP-2040 Demand Parameters ..............24 Table 4-3: VP-2040 Energy Parameters ..............25 Table 5-1: VP-2040 Analog Output Parameters ............32...
  • Page 9: Chapter 1 - Introduction

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 1 - Introduction General Information The power quality meter as Enhanced IED VP-2040 is an ideal device to power monitoring in power quality when continuous monitoring to a power system is required.
  • Page 10: Features

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Features VP-2040 is a multi-functional power meter, integrating data acquisition and control into a whole. It can take the place of numerous meters, relays, transducers, and other components.
  • Page 11: Standard Features

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual  2 controlled relay outputs  1 analog output to a transducer function  2 pulse outputs based on KWH, KVarH, KVAH or AH ...
  • Page 12: Set-Points To Alarms

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 1.2.4 Set-points to Alarms Any of the assignable output relays may be used to trigger and alarm for specific applications. Table 1-1: VP-2040 Set-points condition table...
  • Page 13: Power Conventions

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Power Conventions Based on bellow diagram the VP-2040 can calculate all of power electric parameters that used in industry. Power Meter VP-2040 IED Figure 1-1: VP-2040 E-IED Metering Conventions 1.3.1...
  • Page 14: Ied Options

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual WH (±) 3 phase active energy VarH (±) 3 phase reactive energy 3 Phase total power factor PF1 / PF2 / PF3 3 phase individual power factor...
  • Page 15: Event Logger

    VP-2040 Enhanced IED Chapter 1 - Introduction V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual harmonic spectrum are useful and available with the power analysis option. 1.5.2 Event Logger Alarms, set-point triggers, input and output events can be stored in a 50 event record and time / date stamped by the internal clock.
  • Page 16: Chapter 2 - Model & Ordering

    VP-2040 Enhanced IED Chapter 2 - Model & Ordering V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 2 - Model & Ordering Overview The VP-2040 Enhanced-IED has some models that during product ordering shall be defined about desired model. In the figure bellow you can see model and ordering forms.
  • Page 17: Chapter 3 - Specifications

    VP-2040 Enhanced IED Chapter 3 - Specifications V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 3 - Specifications VP-2040 Specifications 3.1.1 Measured Power Parameters Display All measured display scaled to primary readout - Display 4 digits to V / A / W / Var / VA / PF...
  • Page 18: Measuring Accuracy

    VP-2040 Enhanced IED Chapter 3 - Specifications V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Burden Voltage < 0.2VA at 600V / phase 0.02VA at 120V / phase Current < 0.1VA at rating Current Overload capacity : 120% x rated continuous...
  • Page 19: Optional Auxiliary Monitoring

    VP-2040 Enhanced IED Chapter 3 - Specifications V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 3.1.4 Optional Auxiliary Monitoring Digital Input (DI) 4 or 8 status input by option choose Internal powered of DC 30V Input / dry contact...
  • Page 20: Data Logger Feature

    VP-2040 Enhanced IED Chapter 3 - Specifications V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 3.1.7 Data Logger Feature Event Logger 50 events with time-stamped in NVRAM Status change of switch input Activation of set-points Alarms Operation of controlled relay output...
  • Page 21: Environment

    VP-2040 Enhanced IED Chapter 3 - Specifications V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 3.1.9 Environment Operating Condition Temperature range: -20 to +60°C Storage Condition Temperature range: -30 to +70°C Humidity Condition RH: 5-95% non-condensed 3.1.10 Power Supply...
  • Page 22: Chapter 4 - Measuring Capability

    VP-2040 Enhanced IED Chapter 4 - Measuring Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 4 - Measuring Capability Real-time based Electrical Parameters The VP-2040 provides voltage, current, power, and frequency etc. basic parameters. The following data are effective real values, and the refresh rate is 1 second.
  • Page 23: Power Factor Symbols

    VP-2040 Enhanced IED Chapter 4 - Measuring Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Power Factor Symbols The symbols of measuring power factor conform to the stipulations of IEC, and the figure below describes the relevant definitions.
  • Page 24: Demand Parameters

    VP-2040 Enhanced IED Chapter 4 - Measuring Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Demand Parameters Demand refers to the value obtained in the following way: the accumulated electrical parameters within a period of time divided by the time length.
  • Page 25: Energy Parameters

    VP-2040 Enhanced IED Chapter 4 - Measuring Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Energy Parameters The VP-2040 can measure bidirectional four-quadrant active and reactive energy, and the maximum accumulated value is up to 99,999,999.9 The decimal place will not show. When the accumulated value reaches to maximum, it will overturn automatically.
  • Page 26: Harmonic Parameters

    VP-2040 Enhanced IED Chapter 4 - Measuring Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Harmonic Parameters The VP-2040 provides optional measurement of complete 31st harmonic for voltage and current as well as their total harmonic content (THD) and K factor of current.
  • Page 27: Chapter 5 - Ied Capability

    VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 5 - IED Capability Status Input The VP-2040 provides 4 or 8 status input channels based on model chooses, which are used to detect state information such as breaker position signals and isolator position signals.
  • Page 28: Relay Output

    VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Relay Output The VP-2040 provides 2 or 4 relay output channels based on model choose. The contact of each relay output is in mode of SPST-NO (Single Pole, Single Throw, and Normally Open).
  • Page 29 VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Also there are the two relay operations modes are as follows: o Normal Operation: that in two difference mode provides:  Remote Control mode: By receiving a command from a PC or PLC, the relay closes.
  • Page 30: Pulse Output

    VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Pulse Output The VP-2040 provides optional two pulse output outlets, one for active energy pulse output and the other for reactive energy pulse output.
  • Page 31 VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual The maximum pulse speed does not exceed 200 ms, which means that, when the accumulated energy of the meter is 1 kwh, the number of pulse outputs is N.
  • Page 32: Analog Output

    VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Analog Output The VP-2040 can provide one optional 4-20mA analog output, supporting the access of the DCS system. The user can, through the communication interface, set the parameter value corresponding to the analog output.
  • Page 33 VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual     Output Output 4 mA 20 mA 4 mA 20 mA         ...
  • Page 34: Alarm System

    VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Alarm System The VP-2040 provides optional multiple relay alarm outputs, any of which can work independently and support the user’s programming. Any of the relay output that has been set at Local Control mode (refer to section 5.2 of this manual for more information) corresponds to...
  • Page 35 VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Alarm Detection Setting Parameter Alarm Record Setting the lower limit in primary reading of Under Frequency Frequency and threshold action time in seconds.
  • Page 36: Sequence Of Event (Soe) Log

    VP-2040 Enhanced IED Chapter 5 - IED Capability V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Sequence of Event (SOE) Log The VP-2040 provides optional function of recording up to 50 records of Sequence of Events (SOE), and the records can be kept for more than 10 years.
  • Page 37: Chapter 6 - Unit Installation

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 6 - Unit Installation Unit Observation The VP-2040 is DIN 96x96 device that install on the front panel of metering cubicles, control cubicles and normally in the medium voltage compartments of any power distribution system components.
  • Page 38: Base Terminal Definitions

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.2.1 Base Terminal Definitions In regarding the only base unit used, there are 2 rows terminal and the terminal numbered from 1 up to 28. Please pay attention that terminal with code (--) tagged as NC (Not Connect), so you should leave this terminal float and disconnect to any wiring.
  • Page 39: Expansion Option A: 4X Status + 4X Relay

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.2.2 Expansion Option A: 4x Status + 4x Relay The option with 4 Status Input and 4 Relay output has bellow terminal definition. The definition table terminal No started from 29.
  • Page 40: Expansion Option B: 8X Status + 2X Relay

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.2.3 Expansion Option B: 8x Status + 2x Relay The option with 8 Status Input and 2 Relay output has bellow terminal definition. The definition table terminal No started from 29.
  • Page 41: Expansion Option E: 8X Status + 2X Pulse

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.2.4 Expansion Option E: 8x Status + 2x Pulse The option with 8 Status Input and 2 Pulse output has bellow terminal definition. The definition table terminal No started from 29.
  • Page 42: Expansion Option P: Profibus Communication

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.2.5 Expansion Option P: PROFIBUS Communication The option with PROFIBUS communication module has bellow terminal definition. The definition table terminal No started from 29.
  • Page 43: Power Supply Connection

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Power Supply Connection A power supply to the VP-2040 can be in two options which should be selected one of them during ordering the component.
  • Page 44: Voltage To Pt Inputs

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Voltage to PT inputs The VP-2040 allows input voltage range from 0~400Vac between voltage inputs (V1, V2, V3) and voltage neutral (VN). These inputs can be direct connected or supplied via from external PTs.
  • Page 45: Shielding Ground

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Shielding Ground The input and output wiring to the VP-2040 for AO, PO, RS485 comport are required to use shielding cable “the shielding ground (SHLD) should be with one end ground at VP-2040 end only or at SCADA / PLC / Computer only”...
  • Page 46: Figure 6-4: Vp-2040 Rs-485 Communication Wiring

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Master (Computer / RTU) RS-485 (*) Z = Terminating Impedance at each end (typically R=120 Ohms and C=1nF) Up to 32 Ground shield at...
  • Page 47: Wiring Diagrams

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Wiring Diagrams 6.8.1 High Voltage, 3 Phase, 4 Wires, Star, 3PT/3CT L (+) N (-) Contacts Power Digital Supply Input VP-2040 Current Input...
  • Page 48: High Voltage, 3 Phase, 3 Wires, Delta, 2Pt/3Ct

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.8.2 High Voltage, 3 Phase, 3 Wires, Delta, 2PT/3CT L (+) N (-) Contacts Power Digital Supply Input VP-2040 Current Input Digital Relay 1...
  • Page 49: High Voltage, 3 Phase, 3 Wires, Delta, 2Pt/2Ct

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.8.3 High Voltage, 3 Phase, 3 Wires, Delta, 2PT/2CT L (+) N (-) Contacts Power Digital Supply Input VP-2040 Current Input Digital Relay 1...
  • Page 50: Low Voltage, 3 Phase, 4 Wires, Star, 3Ct

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.8.4 Low Voltage, 3 Phase, 4 Wires, Star, 3CT L (+) N (-) Contacts Power Digital Supply Input VP-2040 Current Input Digital Relay 1...
  • Page 51: Low Voltage, 3 Phase, 3 Wires, Delta, 3Ct

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.8.5 Low Voltage, 3 Phase, 3 Wires, Delta, 3CT L (+) N (-) Contacts Power Digital Supply Input VP-2040 Current Input Digital Relay 1...
  • Page 52: Low Voltage, 3 Phase, 3 Wires, Delta, 2Cts

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.8.6 Low Voltage, 3 Phase, 3 Wires, Delta, 2CTs L (+) N (-) Contacts Power Digital Supply Input VP-2040 Current Input Digital Relay 1...
  • Page 53: Dimensions

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Dimensions 100 mm 96 mm 65 mm 35 mm Expansion Option 18 mm Front Side View View CUT OUT +0.2 +0.2 x 90...
  • Page 54: Application Configuration Sample

    VP-2040 Enhanced IED Chapter 6 - Unit Installation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 6.10 Application Configuration Sample In this section we describe a sample configuration about VP-2040 Unit used normally configurations substations. The VP-2040 rear network can help utility operator to connect many VP-2040 networked units for Power Quality Monitoring and SCADA application rapidly.
  • Page 55: Chapter 7 - Unit Front Panel Operation

    VP-2040 Enhanced IED Chapter 7 - Unit Front Panel Operation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 7 - Unit Front Panel Operation Unit Observation The VP-2040 has a front display module with small control key pads.
  • Page 56 VP-2040 Enhanced IED Chapter 7 - Unit Front Panel Operation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual The Veesta-Power Measurement 2000 Product Series Trade Mark THD Prompt Higher Harmonic Prompt Phase Sequence & Quadrant Prompt Real-Time Data Display Area...
  • Page 57: Key Pad Function

    VP-2040 Enhanced IED Chapter 7 - Unit Front Panel Operation V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 7.1.2 Key pad function The front keys operate in various conditions; the two main categories are in View mode and Programming mode. In the Programming mode you also have two mode of setting view and modify setting.
  • Page 58: Chapter 8 - Protocol And Communication

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 8 - Protocol and Communication PLC Modbus® Compatible The Modbus® communications protocol allows information and data to be efficiently transferred between the Enhanced-IED VP-2040 series and Modicon programmable logic controller (PLC) or other third party Modbus®...
  • Page 59: Slave Address

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Item Convention Slave Address 1 Character Function Code 1 Character Data field N Characters Error Check 16 bit CRC ≧ End of Frame...
  • Page 60: Modbus Framing

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual means of checking for errors. No response is transmitted if any error has occurred. Modbus Framing Modbus Message Format is as bellow:...
  • Page 61: Error Check Filed

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual start at and how many to read. The imbedded address and data information varied with the type and capacity of slave associated with the slave.
  • Page 62: Algorithm

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual 8.4.6 CRC-16 Algorithm Once the following algorithm is complete, the working register “A” will contain the CRC value to be transmitted. Note that this algorithm requires the characteristic polynomial to be reverse bit ordered.
  • Page 63: Supported Function Codes

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Supported Function Codes 8.5.1 Function Code 3 (03H) - Read Holding registers The VP-2040 implementation of Modbus®, these commands can be used to read any set-point (" holding registers ") or actual value ("...
  • Page 64: Function Code 5 (05H) - Execute Operation

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Example Slave Response Bytes Meaning (hex) Slave Address Message from slave 01 Function Code Read registers Byte Count 3 registers = 6 bytes...
  • Page 65: Function Code 16 (10H) - Write Multiple Registers

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Example Slave Response Bytes Meaning (hex) Slave Address Message for slave 1 Function Code Execution Operation Operation Code Relay 1 Command Code Value...
  • Page 66 VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Master Example Bytes Meaning Transmission (hex) Slave Address Message for slave 01 Function Code Store Multiple Setpoint (function 16) Data Starting Setpoint address 41003...
  • Page 67: Error Responses

    VP-2040 Enhanced IED Chapter 8 - Protocol and Communication V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Error responses When VP-2040 detects an error other than a CRC error, a response will be sent to the master. The MSBit of the function code byte will be set to 1 (i.e.
  • Page 68: Chapter 9 - Register Map Profile

    VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Chapter 9 - Register Map Profile Introduction This chapter describes about Modbus Register Map table and profile. To have better view on all of parameters of VP-2040 you must consider bellow items to communicating and translating data of registers.
  • Page 69 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Table 9-1: VP-2040 Data Conversion Formula Item Engineering Value Unit Type Note U = Rx * PTR * 0.01 Ua, Ub, Uc, UP_av,...
  • Page 70: Memory Map Data Format

    VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Memory Map Data Format Data format of each memory register value of VP-2040 based on its meaning is difference with other one. In the last column memory register map table in bellow of this section there is a column named as “FORMAT”.
  • Page 71 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) WORD STRUCTRE - YEAR / MONTH FFFF High Byte = Year: 1 =2001, 2=2002, ……., 99=2099 FFXX Low Byte = Month: 1=January, 2=February, ..., 12=December...
  • Page 72 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) UNSIGNED INTEGER – PULSE OUTPUT PARAMETER 1000- 5000 = For Meter Type of 220V/5A in step of 100...
  • Page 73 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) ( F26 ) 3 = Set-point 3 (Over Voltage Phase C) 0003 4 = Set-point 4 (Under Voltage Phase A)
  • Page 74 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) ( F27 ) BIT 12: Not Used 1000 BIT 13: Not Used 2000 BIT 14: Not Used 4000...
  • Page 75 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) ( F29 ) 12 = Under Voltage Phase A (Set-point 4) 0CXX 13 = Under Voltage Phase B...
  • Page 76 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) UNSIGNED LONG INTEGER – OVER LOAD SET-POINT VALUE FFFFFFFF 0 = Disable Set-Point and Alarm Triggering Function 00000000 Range From: 0.1 kW...
  • Page 77 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual CODING FORMAT DESCRIPTION (HEX) UNSIGNED INTEGER – COMMAND - FUNCTION CODE 5 (05H) FFFF ON / CLOSE / ACTIVE / SET FF00...
  • Page 78: Memory Map Register Table

    VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Memory Map Register Table In Memory Register map table in bellow of this chapter there are some columns which describe about register profile as bellow: ...
  • Page 79 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Table 9-3: VP-2040 Input Registers, Read Only Data REGISTER UNIT SCALE GROUP ADDR ADDR DESCRIPTION FORMAT VALUE RANGE VALUE FACTOR (INDEX) (HEX)
  • Page 80 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY DO STATUS...
  • Page 81 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY VOLTAGE 40101...
  • Page 82 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY APPARENT 40128...
  • Page 83 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY Input Active Energy...
  • Page 84 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY DEMANDS 40301...
  • Page 85 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY HARMONIC 40401...
  • Page 86 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY HARMONIC 40528...
  • Page 87 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY MAXIMUM 40601...
  • Page 88 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY MINIMUM 40616...
  • Page 89 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE RANGE VALUE FACTOR (INDEX) (HEX) Actual Values (Input Registers) READ ONLY EVENT NO...
  • Page 90 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Table 9-4: VP-2040 Holding Registers, Read/Write Data REGISTER FACTORY UNIT SCALE GROUP ADDR ADDR DESCRIPTION VALUE FORMAT DEFAULT VALUE FACTOR INDEX (HEX)
  • Page 91 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER FACTORY UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE DEFAULT VALUE FACTOR INDEX (HEX) RANGE VALUE Programming Values (Holding Registers) READ OR WRITE...
  • Page 92 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER FACTORY UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE DEFAULT VALUE FACTOR INDEX (HEX) RANGE VALUE Programming Values (Holding Registers) READ OR WRITE DATE &...
  • Page 93 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER FACTORY UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE DEFAULT VALUE FACTOR INDEX (HEX) RANGE VALUE Programming Values (Holding Registers) READ OR WRITE...
  • Page 94 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER FACTORY UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE DEFAULT VALUE FACTOR INDEX (HEX) RANGE VALUE Programming Values (Holding Registers) READ OR WRITE...
  • Page 95 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual REGISTER FACTORY UNIT SCALE GROUP DESCRIPTION FORMAT ADDR ADDR VALUE DEFAULT VALUE FACTOR INDEX (HEX) RANGE VALUE Programming Values (Holding Registers) READ OR WRITE...
  • Page 96 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Table 9-5: VP-2040 Coil Registers, Write Data, Execution Command GROUP DESCRIPTION ON DATA OFF DATA FORMAT ADDR ADDR INDEX (HEX) Programming Values (Coil Register)
  • Page 97 VP-2040 Enhanced IED Chapter 9 - Register Map Profile V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual GROUP DESCRIPTION ON DATA OFF DATA FORMAT ADDR ADDR INDEX (HEX) Programming Values (Coil Register) WRITE ONLY Reset Latched Alarm of SET-POINT 22...
  • Page 98: Chapter 10 - Troubleshooting

    In this case before contact to Veesta World Company support center, review this chapter. You may found common problems that may encounter to them.
  • Page 99 VP-2040 Enhanced IED Chapter 10 - Troubleshooting V-PM2000 Series, Veesta Power Measurement Instructions & User's Manual Possible Problem Possible Cause Possible Solution Check if the transformation There is no change in The on-off operating ratio of the PT has been set the on-off status.
  • Page 100 Veesta World Co World Wide Web: http://www.veesta-world.com/ E-Mail: info@veesta-world.com...