Sequence Of Event (Soe) Log - Veesta World V-PM2000 Series User Manual

Enhanced ied, power measurement, power quality and monitoring device
Table of Contents

Advertisement

VP-2040 Enhanced IED
V-PM2000 Series, Veesta Power Measurement
Instructions & User's Manual
5.6

Sequence of Event (SOE) Log

Byte
Definition
0
Type of Event
1
Status of Operation
2 - 3
Milliseconds
4 - 7
Unix Clock
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
The VP-2040 provides optional function of recording up to 50 records
of Sequence of Events (SOE), and the records can be kept for more
than 10 years.
The SOE recording function can record the displacements of switch
contacts. When an event occurs, the meter will automatically record
the type of the event such as closing of status 1. At the same time,
the year, month, day, hour, minute, second, millisecond when the
event occurs will be recorded precisely, and the resolution is 2 ms.
Users can read all the SOE records through communication and
Modbus RTU protocol. For details, refer to Chapter 9 - Register Map
Profile .
A standard structure of SOE event data is as follows:
Table 5-3: VP-2040 SOE Capability
1: S1 Channel 2: S2 Channel 3: S3 Channel 4: S4 Channel
5: S5 Channel 6: S6 Channel 7: S7 Channel 8: S8 Channel
9: Over Voltage Phase A
11: Over Voltage Phase C
13: Under Voltage Phase B
15: Over Current Phase A
17: Over Current Phase C
19: Under Current Phase B
21: Over Frequency
23: Over Load
25: 3x Phase Over Phase Voltage
26: 3x Phase Under Phase Voltage
27: 3x Phase Over Line Voltage
28: 3x Phase Under Line Voltage
29: 3x Phase Over Current
30: 3x Phase Under Current
0: Open Status
Valid only for Type 1~8
Milliseconds Time of event occurrence in one WORD format.
Number of seconds that have elapsed since 00:00:00 in January
1, 1970 in Greenwich Mean Time.
This format also called as Unix Time or POSIX Time or EPOCH
Time
For more information about setting and parameters please refer to
Chapter 9 - Register Map Profile .
Chapter 5 - IED Capability
Description
10: Over Voltage Phase B
12: Under Voltage Phase A
14: Under Voltage Phase C
16: Over Current Phase B
18: Under Current Phase A
20: Under Current Phase C
22: Under Frequency
24: Phase Loss
1: Close Status
Page 36 of 100