VP-2040 Enhanced IED
V-PM2000 Series, Veesta Power Measurement
Instructions & User's Manual
5.5
Alarm System
It.
Alarm Detection
1
Over Voltage Phase A
2
Over Voltage Phase B
3
Over Voltage Phase C
4
Under Voltage Phase A
5
Under Voltage Phase B
6
Under Voltage Phase C
7
Over Current Phase A
8
Over Current Phase B
9
Over Current Phase C
10
Under Current Phase A
11
Under Current Phase B
12
Under Current Phase C
13
Over Frequency
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
The VP-2040 provides optional multiple relay alarm outputs, any of
which can work independently and support the user's programming.
Any of the relay output that has been set at Local Control mode (refer
to section 5.2 of this manual for more information) corresponds to
alarm about voltage or current and etc. Each alarm needs 2
parameters for setting and triggering into memory and creates the
alarm record event and also 3 parameters for trigger an output relay
to act as alarm output status or act as tripping function.
Bellow table shows a list of alarm detection and its individual setting:
Table 5-2: VP-2040 Alarm System Capability
Setting Parameter
Setting the upper limit in primary reading of Voltage
and threshold action time in seconds.
Setting the upper limit in primary reading of
Voltage and threshold action time in seconds.
Setting the upper limit in primary reading of Voltage
and threshold action time in seconds.
Setting the lower limit in primary reading of Voltage
and threshold action time in seconds.
Setting the lower limit in primary reading of Voltage
and threshold action time in seconds.
Setting the lower limit in primary reading of Voltage
and threshold action time in seconds.
Setting the upper limit in primary reading of Current
and threshold action time in seconds.
Setting the upper limit in primary reading of Current
and threshold action time in seconds.
Setting the upper limit in primary reading of Current
and threshold action time in seconds.
Setting the lower limit in primary reading of Current
and threshold action time in seconds.
Setting the lower limit in primary reading of Current
and threshold action time in seconds.
Setting the lower limit in primary reading of Current
and threshold action time in seconds.
Setting the upper limit in primary reading of
Frequency and threshold action time in seconds.
Chapter 5 - IED Capability
Alarm
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Record
Output
Page 34 of 100