VP-2040 Enhanced IED
V-PM2000 Series, Veesta Power Measurement
Instructions & User's Manual
4.
Burden
5.
Current Overload capacity :
6.
Voltage Overload capacity :
3.1.3
Measuring Accuracy
1.
Voltage
2.
Current
3.
Power
4.
Power Factor
5.
Frequency
6.
Active Energy
7.
Reactive Energy
8.
THD
9.
Individual Harmonic
10.
Unbalance
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
:
Voltage < 0.2VA at 600V / phase
0.02VA at 120V / phase
Current < 0.1VA at rating
120% x rated continuous
10 x rated 1 seconds
25 x rated 2 seconds / 50 x rated 1 seconds
120% rated continuous
2x rated 1 seconds
:
Accuracy: 0.2%
Measuring Range:
- Directly: 300Vph-N, 520Vph-ph
- PT primary: 0~499,999V
- PT secondary: 57.7Vph-N, 100Vph-ph
:
Accuracy: 0.2%
Measuring Range:
- CT primary: 0~49,999A
- CT secondary: 1 A or 5A
:
Accuracy: 0.5%
Measuring Range: Each phase: 0~100 MW/Mvar
:
Accuracy: 0.5%
Measuring Range: -1.000 ~ +1.000
:
Accuracy: 0.01
Measuring Range: 35~ 65 Hz
:
Accuracy: 1.0%
Measuring Range: 0~ 99,999,999.9 kWh
:
Accuracy: 2.0%
Measuring Range: 0~ 99,999,999.9 kVarh
:
Accuracy: 1.0%
Measuring Range: 0~100.0%
:
Accuracy: 1.0%
Measuring Range: 0~100.0%
:
Accuracy: 1.0%
Measuring Range: 0~100.0%
Chapter 3 - Specifications
Resolution: 0.01 V
Resolution: 0.001 A
Resolution: 0.1 W/Var
Resolution: 0.001
Resolution: 0.01 Hz
Resolution: 0.1 kWh
Resolution: 0.1 kWh
Resolution: 0.001
Resolution: 0.001
Resolution: 0.001
Page 18 of 100