VP-2040 Enhanced IED
V-PM2000 Series, Veesta Power Measurement
Instructions & User's Manual
5.4

Analog Output

VP-2040 with 1x Analog Output option
Parameter
Phase Voltage
Voltage
Current
Active Power
Reactive Power
Power Factor
Frequency
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
The VP-2040 can provide one optional 4-20mA analog output,
supporting the access of the DCS system. The user can, through the
communication interface, set the parameter value corresponding to
the analog output. The maximum load resistance of the interface
should not exceed 500 Ohms.
(Positive Terminal)
Load
Metering
(Negative Terminal)

Figure 5-4: VP-2040 Analog Output Capability

On some sites, due to different transmission cables or loading
conditions, the analog output at the high end appears to be non-
linear. VP-2040 provides a settable magnification factor. By
modifying the magnification factor, the user can adjust the proportion
factor of the output curve.
The analog output can be set as any of the items in the table below:
Table 5-1: VP-2040 Analog Output Parameters
Value Type
1- Phase A Voltage, 2- Phase B Voltage, 3- Phase C Voltage
1- Line A-B Voltage, 2- Line B-C Voltage, 3- Line C-A Voltage
1- Phase A Current, 2- Phase B Current, 3- Phase C Current
Total Active Power
Total Reactive Power
Total Power Factor
System Frequency
In the figure below shows the analog output characteristic curve, and
the magnification factor is λ.
Chapter 5 - IED Capability
01100100
Digital to Analog
Converter
Page 32 of 100