4.3

Demand Parameters

The computation is updated when
each computing intervals ends
15 minutes
computing interval
15
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
Demand refers to the value obtained in the following way: the
accumulated electrical parameters within a period of time divided by
the time length. To facilitate the operation of the user, VP-2040
adopts the fixed-block calculation method in the fixed period of time,
and the period of time is fixed, being 15 minutes.
VP-2040 provides the following demand data and measuring ranges:
Table 4-2: VP-2040 Demand Parameters
Demand Reading
Demand Current
Three-phase average value
Maximum peak
Active Power / Reactive Power / Apparent Power
Three-phase average value
Maximum peak
The figure below describes demand calculation:
15 minutes
computing interval
Fixed blocks
30

Figure 4-2: VP-2040 Power Factor Symbols

Chapter 4 - Measuring Capability
Measuring Range
0 – 50,000 A
0 – 50,000 A
0 - ± 100 MW / Var / VA
0 - ± 100 MW / Var / VA
The demand value is the
average value when the
last computing intervals
end.
15 minutes
computing interval
45
Time (minutes)
Page 24 of 100