3.0 OPERATION
Front Panel Controls and Indicators (continued)
Switch

Description

Position
0
Equalize 1
1
Equalize 2
2
Deep Cell Lead Acid 2
3
Not Specified
4
Gel Cell 2
5
Gel Cell 1
6
PbCa–Lead Acid
Deep Cycle Lead Acid 1
7
(Default Setting)
8
NiCad 1
9
NiCad 2
NOTES:
Switch positions "0" and "1" are for monthly battery maintenance only. Return the switch to the appropriate position for the system's batteries when
Equalize charging has completed. NEVER EQUALIZE SEALED BATTERIES! Use together with BATTERY CHARGER RATE potentiometer
(position 1) or BATTERY CAPACITY potentiometer (position 0).
Equalize voltages are displayed in the table with an asterisk (*)–switch positions "0" and "1" only.
Switch position "7" is the default value as shipped from the factory.
Always refer to the battery manufacturer's specifications for Float, Bulk and Equalize (if applicable) voltages.
12 Volt Models
24 Volt Models
Float
Bulk/Equalize*
Float
Voltage
Voltage
Voltage
13.2
*15.0
26.4
13.2
*15.5
26.4
13.3
15.0
26.6
13.6
14.3
27.2
13.7
14.4
27.4
13.5
14.1
27.0
13.2
14.3
26.4
13.4
14.6
26.6
14.0
16.0
28.0
14.5
16.0
29.0
Equalize
Bulk/Equalize*
Charge
Voltage
Rate
Battery
Capacity
6 hours minimum
*30.0
Setting
12 hours maximum
(C/40)
Battery
Charger
6 hours minimum
*31.0
Rate Setting
12 hours maximum
(manual)
30.0
28.6
28.8
28.2
28.6
29.2
32.0
32.0
Time
975-0012-014