Electrical installation

8.1.3 Specifications of standard wiring components

8.2 To connect the electrical wiring to the indoor unit

Installer reference guide
36
Wire type
Single-core wire
Stranded conductor wire
with round crimp-style
terminal
Tightening torques
Item
M4 (X1M)
M4 (earth)
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
Component
Interconnection cable (indoor↔outdoor)
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
c b
A
a
a Curled single-core wire
b Screw
c Flat washer
c b
B
a
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
1-3
Installation method
AA´
c
a
a
b
c
B
Tightening torque (N•m)
1.2
4-core cable 1.5 mm²~2.5 mm²
and applicable for 220~240 V
H05RN-F (60245 IEC 57)
Daikin room air conditioner
4P518023-14L – 2022.06