Daikin FTXP71N2V1B Installer's Reference Manual page 37

Hide thumbs Also See for FTXP71N2V1B:
Table of Contents

Advertisement

FTXP-N
Daikin room air conditioner
4P518023-14L – 2022.06
NOTICE
Keep the power line and transmission line apart from each other. Transmission
wiring and power supply wiring may cross, but may NOT run parallel.
In order to avoid any electrical interference, the distance between both wirings
should ALWAYS be at least 50 mm.
Electrical work should be carried out in accordance with the installation manual
and the national electrical wiring rules or code of practice.
1 Set the indoor unit on the mounting plate hooks. Use the " " marks as a
guide.
c
a Mounting plate (accessory)
b Interconnection cable
c Wire guide
2 Pass the interconnection cable from the outdoor unit through the feed-
through wall hole, through the back of the indoor unit and through the front
side.
Note: In case the interconnection cable was stripped in advance, cover the ends
with insulating tape.
3 Bend the end of the cable up.
a Terminal block
b Electrical component block
c Cable clamp
4 Strip the wire ends approximately 15 mm.
5 Match wire colours with terminal numbers on the indoor unit terminal blocks
and firmly screw the wires to the corresponding terminals.
6 Connect the earth wire to the corresponding terminal.
7 Firmly fix the wires with the terminal screws.
8 Pull the wires to make sure that they are securely attached, then retain the
wires with the wire retainer.
9 Shape the wires so that the service cover fits securely, then close the service
cover.
a
b
8
Electrical installation
|
a
b
c
Installer reference guide
37