Examining The Installation Site; Weight Support; Temperature And Humidity; Cleanliness - H3C SecPathT5030 Installation Manual

Intrusion prevention system
Table of Contents

Advertisement

Examining the installation site

The device can only be used indoors. To ensure correct operation and a long lifespan for your device,
the installation site must meet the following requirements.

Weight support

Make sure the floor can support the total weight of the rack, chassis, modules, and all other
components. For weights of the chassis and components, see "Appendix A Chassis views and
technical specifications."

Temperature and humidity

Maintain temperature and humidity in the equipment room at levels as described in
Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical
property change of materials, and metal corrosion.
Lasting low relative humidity can cause washer contraction and ESD and bring problems
including loose captive screws and circuit failure.
High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the device.
Table 2 Temperature/humidity requirements
Temperature
Operating:
Without drives: 0°C to 45°C (32°F
to 113°F)
With drives: 5°C to 40°C (41°F to
104°F)
Storage: –40°C to +70°C (–40°F to
+158°F)

Cleanliness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points, especially when indoor relative humidity is low. In the worst
case, electrostatic adsorption can cause communication failure.
Table 3 Dust concentration limit in the equipment room
Substance
Dust particles
NOTE:
Dust particle diameter ≥ 5 µm
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion
and premature aging of components, as shown in
Relative humidity
Operating:
Without drives: 5% RH to 95% RH, noncondensing
With drives: 10% RH to 90% RH, noncondensing
Storage: 5% RH to 95% RH, noncondensing
Concentration limit (particles/m
≤ 3 × 10
4
(No visible dust on desk in three days)
Table
4.
3
Table
2.
3
)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Secpatht5060Secpatht5080Secpatht5000-sSecpatht5000-c

Table of Contents