9.7.3 Regulator with humidity sensor

Humidity adjustment via a humidity sensor is made by setting:
• CFG = 2; CFG = 3; CFG =4 or
• CFG = 7; CFG = 8; CFG = 9.
The outlet produces humidity with the following logic:
Production
Humidity
100%
r6
r5
0%
IA1
SP
SP-r0
SP-r0-r4
ID2
Closed
Open
• If the sensor reading is less than SP-r0-r4,thenthehumidityproductionisatitsmaximum;
• If the sensor reading is between SP-r0-r4 and SP-r0,thentheproductionisproportionalbetweenr5 and r6;
• If the sensor reading is between SP-r0 and SP then there is little or no production;
• Mistral does not produce humidity under any other conditions;
• Mistral does not produce any humidity with the sensor in error.

9.8 RECORDING HOURS OF OPERATION

The Mistralhumidifier,amongitsfunctions,includesrecordingtheoperatinghours,tomonitorandalertyouwhentoperform
routine maintenance. Some of the recordings made include:
• Partialhoursofmist-makeroperation;
• Partial hours of fan operation.
The operating hours are stored in the internal memory.
Thisisreferredtoaspartialhours,astherecordedoperatinghourscanberesettozero.
Toview/resetthepartialoperatinghours,youneedtoconnecttheremoteuserinterface(see"1.6 ACCESSORIES" ON PAGE 10).

9.8.1 Mist-maker operating hours: partial number

Ifthemist-makeroperatinghours>A10,theEHUC humidifier will generate a warning. If A10=0,nowarningisgenerated.
The data is considered partial because it can be reset by pressing and holding button T1 for at least 4 seconds.
To view and reset the partial operating hours of the fan see "7.2.5 MAINTENANCE MENU" ON PAGE 37

9.8.2 Fan operating hours: partial number

Ifthefanoperatinghours>A13,theEHUC humidifier will generate a warning. If A13=0,nowarningisgenerated.
The data is considered partial because it can be reset by pressing and holding button T1 for at least 4 seconds.
To view and reset the partial operating hours of the fan see "7.2.5 MAINTENANCE MENU" ON PAGE 37
924EHUCE4.00 - Mistral Humidifier
r4
Fig. 43. Adjustment with humidity sensor
| 49 |