Example 100% Humidity Setpoint:
LED
LED ON/OFF
Humidity value

9.5 MAXIMUM STEAM PRODUCTION CONFIGURATION

Duringnormaloperation,toconfigurethemaximumsteamproductionpressthe
Each time the
buttonispressed,thehumidityvalueisincreasedby5%.
Wait 5 seconds after last pressing the
The humidity percentage values corresponding to the lit LEDs are:
LED
Humidity value

9.6 TEMPERATURE SENSOR

A sensor is installed on the board to measure the temperature of the water in the reservoir during normal operation.
The internal temperature sensor is used by the humidifier for any temperature alerts (see "14.1 ALERTS TABLE (LED
INTERFACE)" ON PAGE 60).
If A1=0,thehightemperaturealertisdisabled.
If A1>0,Mistral generates the alert when the temperature detected by the internal sensor exceeds threshold A1 for a time A2.
In this situation the humidifier empties the reservoir and fills it again.
Ifafteremptying,thealertoccursagainwithinatimeA3,ahightemperaturealertissignalled.
If,instead,afteratimeA3,noalertisgenerated,thepreviouseventiscleared.
If A3=0,noemptyingiscarriedoutandthealertisgeneratedimmediately.