6.3 Wiring diagrams
6.3.1 Connection with ON/OFF humidistat
TERMINALS
1
Connection with voltage-free contact
2
Connection with voltage-free contact
3
No connection (N.C.)
4-5
Short-circuiting
6.3.2 Connection with humidistat with voltage output, ON/OFF and proportional
Fig. 21. Wiring diagram with humidistat with voltage output, ON/OFF and proportional
TERMINALS
1
No connection (N.C.)
2
Connection with humidistat analogue output (+)
3
Connection with humidistat analogue output (-)
4-5
Short-circuiting
The humidifier has an analogue input 0...12 Vdc. Contact the ELSTEAM sales office for other configurations.
924KTE4.01 - KT series humidifiers
5
4
3
Fig. 19. Auxiliary terminal block M1
Fig. 20. Wiring diagram with ON/OFF humidistat