Available Modbus Commands And Data Areas; Address Configuration; Connections; Modbus Tables Content - Elsteam MISTRAL Use And Maintenance Manual

Ultrasonic humidifiers of small size and capacity
Table of Contents

Advertisement

13.3.1 Available Modbus commands and data areas

The commands implemented are as follows:
Command
Description
03 (hex 0x03)
Resource reading command
06 (hex 0x06)
Resource writing command

13.4 ADDRESS CONFIGURATION

TheRS-485communicationserialportcanbeusedtoconfigurethedevice,theparameters,thestatusesandtheModbus
variables and to monitor device operation using Modbus protocol.
The address of a device within a Modbus message is set by the MODBUS Address parameter.
The address 0isonlyusedforbroadcastmessages,recognisedbyallslaves.Slavedevicesdonotrespondtoabroadcast
message.
Seriallineconfigurationparameters,whichcanbeaccessedviatheuserinterfacemenu,are:
Par.
Description
LA1
Modbus protocol controller address.
The RS-485 RTU serial line has the following characteristics (which cannot be changed):
• RTU mode;
• Parity: Even;
• Baudrate: 9600;
• Bit: 8 bit;
• Stop bit: 1 bit.

13.5 CONNECTIONS

Fortheentiresystemtoworkproperly,includingtheRS-485RTUserialline,observetheinstructionsprovidedinchapter"6.
ELECTRICAL CONNECTIONS" ON PAGE 29.
Inparticular,makesuretheconnectionsareperformedcorrectly,observingtheinstructionsinsection
"6.3 WIRING DIAGRAM" ON PAGE 31.

13.6 MODBUS TABLES CONTENT

Table content description
The table below contains the information required to access the resources properly and directly.
There is a table:
• Modbusaddresstable,whichcontainsalltheconfigurationparametersforthedeviceandthecorrespondingModbus
addresses.
Description of columns in the Table of addresses
• Par.:Listofconfigurabledeviceparameters;
• Description: Indicates parameter operation and any possible selections;
• MU: Measurement unit relating to the parameter;
• Range: Describes the interval of values that the parameter can assume. This can be correlated with other instrument
parameters (indicated with the parameter code).
NOTE: if the actual value is outside the permitted limits for that parameter (for example, because other parameters
defining the aforementioned limits have been altered), the value of the violated limit is displayed instead of the actual
value;
• Val. Adr.: Indicates the address of the Modbus register containing the resource you want to access;
• R/W: Indicates the option of reading or writing the resource:
• R: The resource is read-only;
• W: The resource is write-only;
• R/W: The resource can be both read and written.
• CPL:WhenthefieldsindicatesY,thevaluereadbytheregisterneedstobeconvertedbecausethevaluerepresentsa
number with a sign. In the other cases the value is always positive or zero.
• DATA SIZE: Indicates the size in data bits:
• WORD = 16 bit
• Byte = 8 bit
• The "n" bits = 0...15 bit depending on the value of "n"
924EHUCE4.00 - Mistral Humidifier
MU
---
| 58 |
Range
Default
1...247
20
06/2022