6.2.2 Wiring guidelines

Whenwiringthecontrollers,observethefollowingstandards:
•  T heI/Oandcommunicationwiringmustbekeptseparatefromthepowersupplywiring.Thesetwotypesofwiringmust
be routed in separate ducts.
• Makesuretheoperatingenvironmentandconditionsfallwithinthespecifiedvalues.
• Usewireswiththecorrectdiameter,suitedtothevoltageandcurrentrequirements.
• Use copper conductors (compulsory).
• Use shielded twisted pair cables for analogue/digital I/O connections.
Use correctly earthed shielded cables for all analogue inputs and for communication connections. If shielded cables are not
usedfortheseconnections,electromagneticinterferencemaycausesignaldegradation.
Degraded signals can result in unpredictable operation of the controller or the modules and connected equipment.
MALFUNCTIONING OF THE EQUIPMENT
• Perform the wiring carefully and in compliance with electromagnetic compatibility and safety requirements.
• Makesurethewiringiscorrectfortheendapplication.
• Minimisethelengthoftheconnectionsasmuchaspossible,toavoidwindingthecablesaroundelectricallyconnectedparts.
• Beforeapplyingthepowersupply,checkallthewiringconnections.
• Donotconnectcablestounusedterminalsand/orterminalsmarkedwiththetext"Noconnection"(N.C.).

6.2.3 Guidelines for screw terminal blocks

Suitable wiring for the power supply
RISK OF ELECTRIC SHOCK
• Cutoffthepowersupplytoallequipment,includinganyconnecteddevices,beforeremovinganycoversorhatches,or
beforeinstalling/uninstallingaccessories,hardware,fuses,cablesorwires.
• AlwaysuseaproperlycalibratedVoltmetertomakesurethesystemispoweredoff.
Step 5.08 mm (0.199 in.)
7
mm
0.28
in.
mm
2
0.2...2.5
0.2...2.5
AWG
24...14
24...14
Suitable wiring for I/O SELV
Step 3.5 mm (0.137 in.)
7
mm
0.28
in.
mm
2
0.14...1.5
0.14...1.5
AWG
25...15
25...15

6.2.4 Permitted cable lengths

MALFUNCTIONING OF THE EQUIPMENT
• Whenconnectingthepowersupply,usecablesthatarenolongerthan10m(32.80ft.).
• Whenconnectingthesensors,digitalinputsandanalogueinputs,usecablesthatarenolongerthan10m(32.80ft.).
• WhenconnectingtheRS-485serialline,usecablesthatarenolongerthan1000m(3280ft).
• Whenconnectingthedigitaloutputs,usecablesthatarenolongerthan10m(32.80ft).
924EHUCE4.00 - Mistral Humidifier
0.25...2.5
0.25...2.5
2 x 0.2...1
22...14
22...14
2 x 24...18
Fig. 16. Suitable wiring for the power supply
0.25...1.5
0.25...0.5
2 x 0.08...0.5
22...15
22...20
2 x 28...20
Fig. 17. Suitable wiring for I/O SELV
WARNING
DANGER
2 x 0.5...1.5
2 x 0.2...1.5
2 x 0.25...1
2 x 20...16
2 x 24...16
2 x 22...18
2 x 0.5...0.5
2 x 0.08...0.5
2 x 0.25...0.34
2 x 28...20
2 x 23...21
2 x 20...20
NOTICE
| 30 |
C
Ø 3.5 mm (0.14 in.)
N•m
C
Ø 3.5 mm (0.14 in.)
lb-in
N•m
0.5...0.6
lb-in
4.42...5.31
0.5...0.6
4.42...5.31
06/2022

Advertisement

Table of Contents
loading

Table of Contents