Electrical Connections

Caution: Failure to fully open terminal jaws before
removing wire may permanently damage instrument.
Wiring Procedure
1. Remove 0.5 - 0.625 in. (13-16 mm) of insulation from wire
end.
2. Press the orange terminal lever downward with a small
screwdriver to open terminal jaws.
3. Insert exposed (non-insulated) wire end in terminal hole
until it bottoms out.
4. Release orange terminal lever to secure wire in place.
Gently pull on each wire to ensure a good connection.
Wiring Removal Procedure
1. Press the orange terminal lever downward with a small
screwdriver to open terminal jaws.
2. When fully open, remove wire from terminal.
Wiring Tips:
Do not route sensor cable in conduit containing AC power
wiring. Electrical noise may interfere with sensor signal.
Routing sensor cable in grounded metal conduit will help
prevent electrical noise and mechanical damage.
Seal cable entry points to prevent moisture damage.
Only one wire should be inserted into a terminal. Splice
double wires outside the terminal.
Sensor Input Connections
page 2
2
1
FP90-1 Terminals
Sensr Gnd
9
(SHIELD)
Sensr IN
8
(RED)
Sensr V+
7
(BLACK)
FP90-2 Terminals
Sensr Gnd
13
(SHIELD)
Sensr IN
12
(RED)
Sensr V+
11
(BLACK)
FP90-3 Terminals
Snsr 2 Gnd
16
(SHIELD)
Snsr 2 IN
15
(RED)
Snsr 2 V+
14
(BLACK)
Snsr 1 Gnd
13
(SHIELD)
Snsr 1 IN
12
(RED)
Snsr 1 V+
11
(BLACK)
Maximum cable length is 200 ft. for FP5100, FP5200, FP5300,
FP6000 and any sinusoidal À ow signal.
FP90-1, -2
Flow
Fl ow 6. 25 GPM
T ot al 1234567. 8>
ENTER
” 200 ft. (61 m)
B
FP90-1, -2
Flow
Fl ow 6. 25 GPM
T ot al 1234567. 8>
ENTER
” 1000 ft. (300 m)
B
A
B
Maximum cable length is 1000 ft. for FP-5600/FP8501,FP2540/
FP3-1500, FMG-3000 and FMG-550 and any square wave À ow
signal.
No Aux Power:
FP-5100
FP-5200
FP-5300
FP-6000
FP-8500
FP-8501
All sensors
No Aux Power:
FP-5100
FP-5200
FP-5300
FP-6000
FP-8500
FP-8501
OMEGA FP90 Series Flow Transmitter Instructions
FP90-3
Flow
Fl ow1: 6. 25 GPM
Fl ow2: 9. 75 GPM
A
ENTER
A
200 ft. (61 m)
B
200 ft. (61 m)
FP90-3
Flow
Fl ow1: 6. 25 GPM
Fl ow2: 9. 75 GPM
A
ENTER
1000 ft. (305 m)
1000 ft. (305 m)
Aux Power for FP90-1:
FP-5060
FP-5600
FP-8500A
FP-8501A
FP-2541
FMG-3000 Series Magmeter
FMG-550 Series magmeter
Any Open Collector pulse input
Aux Power for FP90-2 must
always be connected to
provide relay power.
Aux Power for FP90-3:
FP-5060
FP-5600
FP-8500A
FP-8501A
FP-2541
FMG-3000 Series Magmeter
FMG-550 Series magmeter
Any Open Collector pulse input