SolarEdge SE3K-RWB Installation Manual page 15

Table of Contents

Advertisement

14
  IMPORTANT SAFETY INSTRUCTIONS
NOTE
The inverter is IP65 rated . Unused conduit openings and glands should be
sealed with appropriate seals.
NOTE
Use PV modules rated according to IEC 61730 class A.
NOTE
The symbol
symbol is also used in this manual.
NOTE
A SolarEdge inverter may be installed in a site with a generator. SolarEdge
requires installing a physical or electronic interlock, which will signal to the
inverter when the grid has been disconnected. Interlock procurement,
installation, maintenance and support are the responsibility of the installer.
Damage to the inverter due to incorrect interlock installation or use of an
interlock that is incompatible with the SolarEdge system will render the
SolarEdge warranty invalid.
For more information, refer to
https://www.solaredge.com/sites/default/files/se-inverter-
support-of-voltage-sources.pdf.
NOTE
The following warning symbols appear on the inverter warning label:
appears at grounding points on the SolarEdge equipment. This
Risk of electric shock
Risk of electric shock from energy stored in the capacitor. Do not
remove cover until 5 minutes after disconnecting all sources of
supply.
Hot surface – To reduce the risk of burns, do not touch.
Three Phase System MAN-01-00507-4.2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Se4k-rwbSe5k-rwb02-70000402-70000502-700006

Table of Contents