INSTALLATION MANUAL FOR ELECTRIC WIRING

Electric wiring
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped
terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)
Item
Phase Switch breaker
Model
3
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.
INDOOR UNIT
TERMINIAL BLOCK
Connecting cable
is self-provided.
OUTDOOR UNIT
TERMINIAL BLOCK
DANGER OF BODILY INJURY OR DEATH
Circuit breaker
Overcurrent protector
(A)
rated capacity (A)
30
Power cable
is self-provided.
3
1
2
2
3
1
R S T N
WARNING
Power source
wire size
(minimum)
20
4.0mm
Power
380-400V~,50Hz
31
Earth leakage breaker
Switch
Leak
breaker
current
2
30
30mA