AD160S2SM3FA Move and scrap the air conditioning ..22 0150544327...
Page 2
Read the precautions in this manual This appliance is filled with R32. carefully before operating the unit. Service indicator; Read technical Read the operator's manual manual The installation and service of this product shall be carried out by professional personnel, who have been trainedand certified by national training organizations that areaccredited to teach the relevant national competency standards that may be set in legislation.
Page 3
•A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts. A vacuum valve shall be provided to evacuate the interconnecting pipe and/or any uncharged refrigerating system part. •The maximum working pressure is 4.3 MPa.
EUROPEAN REGULATIONS IMPORTANT INFORMATION REGA- CONFORMITY FOR THE MODELS RDING THE REFRIGERANT USED Contains fluorinated greenhouse gases covered by the Kyoto Protocol All the products are in conformity with the following European provision: R32/R410A -Low voltage Directive -Electomagnetic CompatibilitY ROHS The products are fulfilled with the requirements in the directive 2011/65/EU...
Page 5
o not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. he appliance must be stored in a room without continuously operating ignition sources(for examples: open flames, an operating gas appliance or an operating electric heater).
Page 6
Cautions Disposal of the old air conditioner Disposal of the packaging of your new air conditioner Safety Instructions and Warnings...
Page 7
Cautions - The installation of pipe-work shall be kept to a minimum. - Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is smaller than Amin(2m2). - Compliance with national gas regulations shall be observed. - Mechanical connections shall be accessible for maintenance purposes.
Safety Precautions CAUTIONS FOR INSTALLATION CAUTIONS FOR TRANSFER OR REPAIR WARNING...
Page 9
Safety Precautions CAUTIONS FOR OPERATION WARNING CAUTION...
Page 10
3mm. 8. The indoor unit installation height is at least 2.5m. 9. A leakage breaker must be installed. For AD160S2SM3FA ,we can get the 10 different ESP through adjust wired controllerYR-E17,please refer below: static presssure grade (factory default)
Installation Manual For Wire Controller 5. Wiring connections of wire controller: There are three methods to connection wire controller and the indoor units: A.One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master unit through 2 pieces of polar wire B.
INDOOR UNIT TROUBLE SHOOTING LED flash times Wired Contents of Possible reasons of indoor PCB controller Malfunction display LED4 LED3 Sensor disconected or brok- Malfunction of indoor en,or at wrong position,or unit ambient temper- short circuit ature sensor Malfunction of indoor Sensor disconected or brok- unit piping temper-...
Is The Unit Installed Correctly Installation place Electric work When you change your address or the installation place For inspection and maintenance...
(When installing at a place under a high humidity environment, pay sufficient attention to the prevention of dewing such as thermal insulation of the unit. ) Ceiling height shall have the following height. Installation space 100mm 100mm AD160S2SM3FA 50mm Combination 366mm with silent panel Obstacle Avoid installation and use at those places listed below.
Page 20
Installation Procedure Indoor Unit 1. Preparation for suspending the unit a.Size of hole at ceiling and position of hanging bolts AD160S2SM3FA Dimensions A(mm) B(mm) C(mm) D(mm) E(mm) F(mm) Model AD160S2SM3FA 1562 2012 2072 b.Hanger bolts installation 2.Installation of indoor unit...
Page 21
Installation Procedure Drain Pipe Drain Piping Good piping Improper piping The size of drain opening Unit model For unit without water pump 25mm AD160S2SM3FA For unit with water pump...
Page 22
Installation Procedure Drain Pipe Drainage Test Procedures Installation Procedure Air Duct Installation work for air outlet ducts Note Connection of suction, exhaust ducts a.Fresh air inlet b.Exhaust (Make sure to use also the suction.)
Selection of size of power supply and interconnecting wires Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.) AD160S2SM3FA POWER SUPPLY & INDOOR-OUTDOOR CONNECTION: Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by outdoor unit terminal blocks.
Page 24
Address:Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone,Qingdao 266555,Shandong,P.R.C. Contacts: TEL +86-532-88936943; FAX +86-532-8893-6999 Website: www.haier.com...