Main Components - AERMEC VED Series Use And Installation Manual

Fan coil for horizontal and vertical ducted installation
Hide thumbs Also See for VED Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 14

MAIN COMPONENTS

1 Right side (load-bearing structure)
2 Air delivery flanges
3 Heat exchange coil
4 Condensate collection tray /
Front panel (upper)
5 Left side (load-bearing structure)
VED
5
6
7
9
7
6
8
9
DESCRIPTION
System types
The fancoils are designed for 2 and 4
pipe systems with fixed or variable flow
rate, in versions:
- 3 Rows and 4 Rows;
- 3 Rows with 2-row hot water coil for
heating-only.
- 4 Rows with 1-row hot water coil for
heating-only.
Ventilation
Ventilation is controlled via a control
panel (accessory).
The 5-speed fan motor can connect the
control panel to 3 speeds that produce
the optimum useful static pressure for
the system.
HEAT EXCHANGE COIL
Main coil with 3 and 4 rows Heating-
only coil with 1 or 2 rows Battery with
low pressure drops, in copper pip-
ing and corrugated aluminium fins,
blocked via mechanical expansion of
the tubes. The collectors are fitted with
female hydraulic connections and air
vents in the upper part of the coil.
FILTERING SECTION
Air intake filter, easily removable for
periodic cleaning Built with renewable
materials and can be cleaned with a
vacuum cleaner.
6 Vents / discharges on the coil
7 Hydraulic connections
8 Condensate drain
9 Fixing slots
10 Air filter (suction)
11 Filter clip
4
3
2
10
11
10
Filtration class G3. Behaviour to flames
M1 NF F 16-101.
ELECTRIC FAN UNIT
Double suction centrifugal fans with fans
designed for low noise emission.
The fans are directly coupled with the
shaft of the electric motor.
The 5-speed fan motor allows you to
choose the 3 preferred speeds by chang-
ing the settings on the electrical box on
the motor.
The electric motor is cushioned with
elastic supports.
Structure
Made of galvanised sheet iron of a suit-
able thickness. Internal insulation in
Class 1.
The installation slots are positioned at
the rear.
The inlets and outlets are designed to
connect the fancoil to all types of air
ducting.
The outlet includes the coupling flange.
CONDENSATE DISCHARGE
Every device is equipped with a con-
densate collection tray for both vertical
and horizontal installation. The tray has
2 fittings (Ø 16mm) for the discharge
of condensate. The 2 fittings protrude
from the side of the unit.
10 Centrifugal fan
12 Electric motor electrical box
13 Electric motor
14 Front closure panel (lower)
15 Electrical wiring
12
13
14
HYDRAULIC CONNECTIONS
The connections, located on the left hand
side, are female. The coil can be rotated
onsite to reverse the fittings onto the
right side.
Control panel
There are several control panels available
to choose the most suitable for the system.
The full potential of the VED units can
be exploited by combining the control
panels, thermostats and other accesso-
ries of the VMF series.
The thermostats of the VMF series allow to:
- Control a single unit and the accesso-
ries.
- Control a network of 6 units, including
a master with thermostat and control
panel plus 5 slave units equipped with
thermostat, which operate independ-
ently based on the ambient conditions.
- Control of the VED unit in a complex net-
work of up to 64 zones with 6 fancoils
(up to 384 fancoils with a single VMF-E5
control board).
IVEDLJ 1107 - 4880900_01
1
8
15
11
17

Advertisement

Table of Contents
loading

Table of Contents