Ariston NIMBUS COMPACT S NET Manual page 82

Table of Contents

Advertisement

Available languages

Available languages

- 4. Curing Heating + Functional Heating
(floor drying done with variable temperature from 25°C to
55°C for the first 18 days and then at fixed temperature of
55°C for the following 6 days)
60
55
50
45
40
35
30
25
20
15
0
5
10
Period (days)
- 5. Manual
(floor drying done at the setpoint temperature set by the
parameter 17.3.9)
17.8.6 Resistance Power Rating Configuration
set the backup resistance configuration
- 2kW+2kW : if the backup interface module comprizes
2kW+2kW (+2kW) electrical resistances
- 2+4kW: if the backup interface module comprizes
2kW+4kW electrical resistances
17.8.7 Defrost
Test the defrost function ON
17.8.8 TDM Flow Sensor Type.
Set the flow sensor relf recognition or flow meter type
DN15 or DN20 (default for monoblock external units)
Push OK button. Turn the knob and select:
17.9
ENERGY MANAGER STATISTICS
17.10
HP DIAGNOSTICS - 1
17.11
HP DIAGNOSTICS - 2
17.12
HP DIAGNOSTICS - 3
17.13
HP DIAGNOSTICS - 4
Displays the characteristic information of the heat pump
(temperatures, water flow switch status, HP status, etc).
Push OK button. Turn the knob and select:
17.14
ENERGY MANAGER
DIAGNOSTICS -1 INPUT
Displays the values of the system board inputs
17.15
ENERGY MANAGER
DIAGNOSTICS - 2 OUTPUT
Displays the values of the system board outputs
17.16
ERROR HISTORY
Last 10 Errors.
17.17
RESET MENU
Reset Factory Settings.
19
CONNECTIVITY
Press the OK button.
After checking the availability of the Sensys NET service
in your country, follow the instructions in the Sensys NET.
82 / GB
15
20
25
30
Push OK button. Turn the knob and select:
20
BUFFER
20.0
CONFIGURATION
20.0.0 Buffer Activation
Active Buffer mode
20.0.1 Buffer charge mode
- Partial charge (1 sensor)
The buffer charge ends once water reaches set point
temperature only at probe level
- Full charge (2 sensors)
The buffer charge ends once both the buffer probe and
the return probe reach set point temperature.
20.0.2 Buffer setpoint temp. hysteresis
Turn the knob and set the desired value in order to mo-
dify the buffer charge hysteresis.
20.0.3 Buffer setpoint temperature heating
Define the temperature set-point for the buffer charge in
heating in fixed mode.
20.0.4 Buffer setpoint temperature cooling
Define the set-point temperature for the buffer charge in
cooling in fixed mode.
20.0.5 SG Ready Buffer setpoint
Define the set-point temperature for the buffer charge in
SG Ready mode.
20.0.6 Offset of PV Integration Setpoint
Turn the knob and set the desired value in order to
increase the set-point temperature for the buffer charge
during the integration of PV system.
20.0.7 Buffer Setpoint mode
- Fixed
The set-point temperature for the buffer charge is indi-
cated by parameters 20.0.3 or 20.0.4
- AUTO function
The set-point temperature for the buffer charge is auto-
matically calculated based on active heat requests from
the zones
Push OK button. Turn the knob and select:
20.1
diagnostics
Display the values of the buffer temperature probes and
indicate whether the buffer charge is active.
20.2
Statistics