NOTE: Installation with under-floor systems
For under-floor installations, make sure to install a safety device on the heating delivery circuit, as required by DTU 65.11. For the thermostat
hookup, refer to "Electrical connections".
If the delivery temperature is too high, the system stops in both domestic hot water and heating/cooling modes, and the remote control will
report error code 116 "Under-floor heating thermostat open". The system will start again when the manual re-arm thermostat is closed.
3
2
NOTE: The temperature probe to use with the buffer must have the following characteristics:
NTC R (25°C) = 10 KΩ ± 1% - ß (25/85) = 3977 ± 1%
1
VE
5
Legend:
1. Internal unit
2. External unit
3. External sensor
4. High-temperature heating zone
/ Low temperature cooling zone
(with fan coil unit)
5. Buffer
6. System interface
6
65 / GB
4