Emc And Environmental Type Tests - Siemens RUGGEDCOM RS8000H Installation Manual

Hide thumbs Also See for RUGGEDCOM RS8000H:
Table of Contents

Advertisement

RUGGEDCOM RS8000H
Installation Guide
A copy of the Material Declaration is available online at
view/109738831.
Section 6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS8000H has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
EMC and Environmental Type Tests
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
https://support.industry.siemens.com/cs/ww/en/
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth
ground ports
Signal ports
±4 kV line-to-earth, ±2 kV line-to-line
DC Power ports
±2 kV line-to-earth, ±1 kV line-to-line
AC Power ports
±4 kV line-to-earth, ±2 kV line-to-line
Signal ports
DC Power ports
AC Power ports
Earth
ground ports
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
DC Power ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
AC Power ports
30% for 1 period, 60% for 50 periods
100% for 50 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
DC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
AC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Signal ports
30 V Continuous, 300 V for 1 s
Test Levels
±8 kV
±15 kV
20 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV
±4 kV
10 V
10 V
10 V
10 V
100% for 5 periods,
Chapter 6
Certification
Severity Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
3
3
3
4
27

Advertisement

Table of Contents
loading

Table of Contents