"PAr"
CO2hi
CO2lo
CO2st
CO2Sr
VLO
VHI
nLO
nHI
Pstd
Percentage of standard modulation of nominal speed
Pbst
PnGt
Pmed
Phol
Tbst
TCOOL
Cooling setpoint temperature for freeheating management
THEAT
Heating setpoint temperature for freecooling management
Summer season transition temperature for pre-cooling
Test
Winter season transition temperature for antifreeze
Tinv
SPrc
RHnSP
Number of samples to calculate dynamic humidity setpoint
Flife
Relative humidity for Minimum Humidity mode activation Relative
HrLO
Relative humidity upper limit in the comfort range *
Hrst
HrHiF
HrHi
Relative humidity for Maximum Humidity mode activation*
FLUSH
ErHs
Func
FUNCTIONS blocking operation (see dedicated paragraph)
* Available only if the functions feature air quality sensors
DESCRIPTION
Maximum CO2 level *
Minimum CO2 level *
Nominal CO2 level *
Full-scale CO2 *
Minimum control voltage in calibration
Maximum control voltage
Minimum speed in operation
Maximum speed
Percentage of boost/party modulation
Percentage of night modulation
Percentage of intermediate modulation
Percentage of minimum - holiday modulation
Boost/Party Time
management geothermal coil
management geothermal coil
Percentage imbalance between flow rates
Filter service life
humidity lower limit in the comfort range *
Shows the HrHi parameter*
Summer Mode activation
Speed of Low humidity
Lindab reserves the right to make changes without prior notice

19.4 Parameters menu

This menu allows you to modify the operating pa-rameters
of the appliance. With the controller "ON", press "M" and On/
Off simultaneously for 3 seconds. Select the "PAr"menu
using the TOUCH PAD and confirm by pressing "Enter".
Select the parameter to be modified by using the TOUCH
PAD and confirm by pressing Enter". Once the parameter is
selected, the value will be displayed. The value can be
modified using the TOUCH PAD. Press the"M" button once
to return to parameter selection; to exit the menu, press the
"M" button 3 times.
2022-01-28
RHR-CF
RANGE
DEFAULT
1500 - 2000 ppm
1500
400 - 600 ppm
500
900 - 1100 ppm
1000
2000 - 30000 ppm
2000
-10% - +10%
See table 2
-10% - +10%
See table 2
-10% - +10%
See table 2
-10% - +10%
See table 2
100% - 110%
100%
110% - 130%
130%
45% - 100%
70%
35% - 70%
45%
0 - 35%
25%
60 - 240 min
180
10 - 30°C
10 - 30°C
10 - 30°C
10 - 30°C
-20% - +20%
0%
1 - 96
96 (15 min)
30 - 400 days
180 days
20 - 45
40 - 50
On - Off
Off
60 - 80
OFF
On - Off
1 - 4 speeds
2 speed
-
26
20
18
24
25
45
65
-