14.4 Automatic calibration

ONLY WITH AUTOMATIC FLOW RATE CONTROL
SYSTEM INSTALLED
1. Turn on the appliance by pressing the ON/OFF key on
the display.
Fig. 42
2. Press the ON/OFF and "M" Menu keys at the same time
to access the TECHNICAL MENU.
Fig. 43
3. Use the TOUCH PAD to select the installer menu
.
Press the Enter key to confirm
Select the "V" symbol and confirm
The message V1 flashes;
Perform the setting of the fan V1;
access the menu by pressing enter, the display shows:
Fig. 44
V
V V
Press the Enter key to confirm
RHR-CF
set the nominal design
flow rate (m 3 /h) using
+
the TOUCH PAD
.
_