Technical Specifications

The following specifications are important and vital to the correct operation of this product. Failure to adhere to
the specifications will result in any warranty or guarantee that was provided becoming null and void.
Ordering Information
PRT-ADC4-DIN
Power Supply
DC Input Voltage
DC Output Voltage
(DC IN Pass-Through)
DC Output Voltage
(Internally Generated)
Operating Current
Low Voltage Cutout
Low Voltage Restore
Communication
Communications
Inputs
Analog Inputs
Trouble Inputs
Dimensions
Dimensions (L x W x H)
Weight
Operating Conditions
Operating Temperature
Storage Temperature
Humidity
Mean Time Between Failures
(MTBF)
It is important that the unit is installed in a dry cool location that is not affected by humidity. Do not locate the
unit in air conditioning or a boiler room that can exceed the temperature or humidity specifications.
Integrated Control Technology continually strives to increase the performance of its products. As a result these
specifications may change without notice. We recommend consulting our website (www.ict.co) for the latest
documentation and product information.
PRT-ADC4-DIN | Protege DIN Rail 4 Channel Analog Input Expander | Installation Manual
Protege DIN Rail 4 Channel Analog Input Expander
12VDC (+/-10%)
12VDC 0.7A (Typical) Electronic Shutdown at 1.1A
24VDC Electronic Shutdown at 200mA
80mA (Typical)
8.7VDC
10.5VDC
RS-485 Isolated Module Network
4 (4-20mA and 0-10V Input)
10 Bit Resolution
8
156.8 x 90 x 60mm (6.17 x 3.54 x 2.36")
270g (9.52oz)
5˚- 55˚ Celsius (41˚ - 131˚ Fahrenheit)
-10˚- 85˚ Celsius (14˚ - 185˚ Fahrenheit)
0%-85% (Non-Condensing)
784,316 hours (calculated using RFD 2000 (UTE C 80-810) Standard)