Error Code Display Mechanical Diagram Mechanical Layout Technical Specifications New Zealand and Australia European Standards UK Conformity Assessment Mark FCC Compliance Statements Industry Canada Statement Disclaimer and Warranty PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Installation Requirements This equipment is to be installed in accordance with: The product installation instructions ⦁ The Local Authority Having Jurisdiction (AHJ) ⦁ PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
DIN Rail Enclosure Additional DIN Rail Enclosure(s) Controller Reader Expander Dialer’s Earth Ground Connection Input Expander Power Supply Output Expander AC Mains Wiring Earth Ground Link Connection PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Page 7
Note that the DIN rail enclosure earth terminal is connected to the power supply V- terminal. There must be only one single earth grounding point per system. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
PCB. Please check carefully before inserting connectors as incorrect placement can cause damage to the PCB. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
RS-485 network cabling. End of Line Resistors: First Module on RS-485 Network Last Module on RS-485 Network 330R 330R From Next Previous Module Module PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Always refer to the card reader manufacturer for detailed installation guidelines. Up to 400m of Cat 6 UTP 24AWG cable, with paralleled pairs, can be used to connect the card reader and the F/2F reader expander. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Door Lock Outputs: Relay 1N4007 Diode 1N4007 Diode Electric Locking Device DOOR DATA Power Supply for Locking Devices PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Door xxx 02 Door Left Open Left Open Access Door xxx 08 Door Duress None None 'xxx' refers to the Name of the door in the Protege system. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Outputs The reader expander has 8 programmable outputs. These outputs are used for activation of door lock relay circuits (200mA max sink, 24VDC max). PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
The controller has a set limit on the number of modules of each type that it can support. When adding and configuring modules always refer to the Maximum Module Addresses table in the controller installation manual. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
The power indicator is lit whenever the correct module input voltage is applied across the N+ and N- terminals. State Description Constantly on (green) Correct module input voltage applied Constantly off Incorrect module input voltage applied PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
The serial number in the device is not valid. Return the unit to the distributor for replacement. Locked Device The module or system controller is a locked device and cannot communicate on the network. Return the unit to the distributor for replacement. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Reader Connection and 12VDC Pass Through (Port 6) RS-485 Input Reader Connection and Reader Connection and 12VDC Pass Through (Port 1) 12VDC Pass Through (Port 5) PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
The mechanical layout shown below outlines the essential details needed to help ensure correct installation and mounting. All measurements are shown in millimeters. 78.40 Front 78.40 39.20 39.20 Back 67.18 PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Integrated Control Technology continually strives to increase the performance of its products. As a result these specifications may change without notice. We recommend consulting our website (www.ict.co) for the latest documentation and product information. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Radiated disturbance EN 55032:2015 Power frequency magnetic field immunity tests (EN 61000-4-8) EN50131 In order to comply with EN 50131-1 the following points should be noted: PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Page 22
ATTACK, comply with the EN 50131 standards. Tamper protection against removal of the cover as well as removal from mounting is provided by tamper switch. Warning: Enclosures supplied by 3rd parties may not be EN50131-compliant, and should not be claimed as such. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
UK Conformity Assessment Mark General Product Statement The UKCA Compliance Label indicates that the supplier of the device asserts that it complies with all applicable standards. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
NOTE: THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE PARTY RESPONSIBLE FOR COMPLIANCE. SUCH MODIFICATIONS COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT. PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
This class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. CAN ICES-3 (A)/NMB-3(A) PRT-F2F8-DIN | Protege Half DIN Rail 8 Port F/2F Reader Expander | Installation Manual...
Integrated Control Technology Ltd nor its employees shall be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information. In accordance with the ICT policy of enhanced development, design and specifications are subject to change without notice.
Page 27
In accordance with the ICT policy of enhanced development, design and specifications are subject to change without notice.
Need help?
Do you have a question about the PRT-F2F8-DIN and is the answer not in the manual?
Questions and answers