PRT-HRDM-DIN
Protege Half DIN Rail 2 Door Reader Expander
Installation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PRT-HRDM-DIN and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ICT PRT-HRDM-DIN

  • Page 1 PRT-HRDM-DIN Protege Half DIN Rail 2 Door Reader Expander Installation Manual...
  • Page 2 Protege® Logo are registered trademarks of Integrated Control Technology Limited. All other brand or product names are trademarks or registered trademarks of their respective holders. Copyright © Integrated Control Technology Limited 2003-2022. All rights reserved. Last Published: 18-Jun-22 10:30 AM PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 3: Table Of Contents

    Standard Outputs (3 To 8) Beeper Outputs (5 and 8) Address Configuration LED Indicators Status Indicator Fault Indicator Power Indicator Relay Indicators Reader 1/Reader 2 Indicators Input Indicators PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 4 New Zealand and Australia European Standards UK Conformity Assessment Mark UL and ULC Installation Requirements UL/ULC Installation Cabinet Options CAN/ULC-S319 UL294 FCC Compliance Statements Industry Canada Statement Disclaimer and Warranty PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 5: Introduction

    Offline functions including All Users, First 10 Users plus 150 Card Cache and No Users ⦁ Online and remote upgradeable firmware ⦁ Industry-standard DIN rail mounting ⦁ PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 6: Installation Requirements

    The National Electrical Code, ANSI/NFPA 70 ⦁ The Canadian Electrical Code, Part I, CSA C22.1 ⦁ AS/NZS 2201.1 Intruder Alarm Systems ⦁ The Local Authority Having Jurisdiction (AHJ) ⦁ PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 7: Grounding Requirements

    DIN Rail Enclosure Additional DIN Rail Enclosure(s) Controller Reader Expander Dialer’s Earth Ground Connection Input Expander Power Supply Output Expander AC Mains Wiring Earth Ground Link Connection PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 8 Note that the DIN rail enclosure earth terminal is connected to the power supply V- terminal. There must be only one single earth grounding point per system. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 9: Mounting

    A Protege DIN rail module can be removed from the DIN rail mount using the following steps: Insert a flat blade screwdriver into the hole in the module tab clip. Lever the tab outwards and rotate the unit off the DIN rail mount. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 10: Wiring Diagram

    Example Open Collector Output Connection (LED) Please refer to the system controller configuration guide for address programming details. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 11: Dual Stack Connector Warning

    PCB. Please check carefully before inserting connectors as incorrect placement can cause damage to the PCB. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 12: Dc Power & Encrypted Module Network

    RS-485 network cabling. End of Line Resistors: First Module on RS-485 Network Last Module on RS-485 Network 330R 330R From Next Previous Module Module PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 13: Door Access Control

    ⦁ Note: The reader and cable shield wires must be joined at the reader pigtail splice for all MIFARE capable ICT card readers. Older readers which are internally grounded and third-party readers do not require the shield wires to be joined.
  • Page 14: Rs-485 Reader Connection (Entry Only)

    NA and NB terminals of the reader and a second 330 ohm EOL resistor must then be inserted between the source NA and NB terminals at the other end of the wiring. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 15: Wiegand Reader Connection

    Shielded Cable GREEN WHITE ORANGE BROWN Shield is frame BLUE grounded at YELLOW one point VIOLET Readers must also be programmed to operate in dual LED mode. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 16: Multiple Wiegand Reader Connection

    WHITE ORANGE BROWN BLUE YELLOW VIOLET ENTRY SHIELD BLACK Shielded Cable GREEN Data WHITE ORANGE BROWN BLUE Shield is frame grounded at YELLOW one point VIOLET EXIT PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 17: Magnetic Reader Connection

    The following example shows the connection of a normally closed door position monitoring contact to monitor the open, closed, forced and alarm conditions of the door. Standard Door Contact Inputs: PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 18: Door Lock Connection

    The 1N4007 diode shown in the above diagram is supplied with the reader expander and must be installed at the electric strike terminals. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 19: Inputs

    When using the 'No Resistor' configuration the controller only monitors the opened and closed state of the connected input device, generating the alarm (open) and restore (closed/sealed) conditions. No EOL Resistor Input Configuration: PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 20: Trouble Inputs

    Door xxx 02 Door Left Open Left Open Access Door xxx 08 Door Duress None None 'xxx' refers to the Name of the door in the Protege system. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 21: Outputs

    LED 1 (Green) Reader 1 RDxxx:04 LED 2 (Red) Reader 1 RDxxx:05 Beeper Reader 1 RDxxx:06 LED 1 (Green) Reader 2 RDxxx:07 LED 2 (Red) Reader 2 RDxxx:08 Beeper Reader 2 PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 22: Beeper Outputs (5 And 8)

    The card or PIN is not recognized, or the user does not have access to this door. Offline Access Granted 4 Beeps If the module is operating offline from the controller, the reader generates additional beeps whenever it grants access to a user. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 23: Address Configuration

    The controller has a set limit on the number of modules of each type that it can support. When adding and configuring modules always refer to the Maximum Module Addresses table in the controller installation manual. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 24: Led Indicators

    Relay Indicators The relay indicators show the status of the lock output relays. State Description Constantly on (red) Relay output is ON Constantly off Relay output is OFF PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 25: Reader 1/Reader 2 Indicators

    Constantly on (green) Input is in a closed state Continuous flash (red) Input is in a tamper state Continuous flash (green) Input is in a short state PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 26: Error Code Indication

    The serial number in the device is not valid. Return the unit to the distributor for replacement. Locked Device The module or system controller is a locked device and cannot communicate on the network. Return the unit to the distributor for replacement. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 27: Mechanical Diagram

    Reader 2 12VDC Pass Through Reader / Relay Indicators Input Indicators Status Indicators 12VDC Input Reader 1 RS-485 Input Relay Outputs 1-2 12VDC Pass Through 12VDC Pass Through PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 28: Mechanical Layout

    The mechanical layout shown below outlines the essential details needed to help ensure correct installation and mounting. All measurements are shown in millimeters. 78.40 Front 78.40 39.20 39.20 Back 67.18 PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 29: Technical Specifications

    Operating Conditions Operating Temperature UL/ULC 0° to 49°C (32° to 120°F) : EU EN -10° to 55°C (14° to 131°F) Storage Temperature -10˚ to 85˚C (14˚ to 185˚F) PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 30 If combining reader technologies, they must be connected on separate ports. The ICT implementation of OSDP conforms to a subset of the OSDP functionality. For specifications and reader configuration, refer to Application Note 254: Configuring OSDP Readers, available from the ICT website.
  • Page 31: New Zealand And Australia

    New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 32: European Standards

    Tests EMC (operational) according to EN 55032:2015 Radiated disturbance EN 55032:2015 Power frequency magnetic field immunity tests (EN 61000-4-8) EN50131 In order to comply with EN 50131-1 the following points should be noted: PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 33 ATTACK, comply with the EN 50131 standards. Tamper protection against removal of the cover as well as removal from mounting is provided by tamper switch. Warning: Enclosures supplied by 3rd parties may not be EN50131-compliant, and should not be claimed as such. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 34: Uk Conformity Assessment Mark

    UK Conformity Assessment Mark General Product Statement The UKCA Compliance Label indicates that the supplier of the device asserts that it complies with all applicable standards. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 35: Ul And Ulc Installation Requirements

    UL/ULC Installation Cabinet Options), installed inside the protected premise, and are UL 294 Listed for Attack Class I applications only. Exit devices and wiring must be installed within the protected area. ⦁ PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 36 The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom. Performance Levels Destructive Attack Line Security Endurance Standby Power PRT-HRDM-DIN Level I Level I Level IV Level I PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 37: Fcc Compliance Statements

    NOTE: THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE PARTY RESPONSIBLE FOR COMPLIANCE. SUCH MODIFICATIONS COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT. PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 38: Industry Canada Statement

    This class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. CAN ICES-3 (A)/NMB-3(A) PRT-HRDM-DIN | Protege Half DIN Rail 2 Door Reader Expander | Installation Manual...
  • Page 39: Disclaimer And Warranty

    Integrated Control Technology Ltd nor its employees shall be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information. In accordance with the ICT policy of enhanced development, design and specifications are subject to change without notice.
  • Page 40 In accordance with the ICT policy of enhanced development, design and specifications are subject to change without notice.