When the EIA-485 shield is in full conduit: The EIA-485 loop allows the FACP to

When the EIA-485 shield is in full conduit:

When the EIA-485 shield is in full conduit:
When the EIA-485 shield is in full conduit:
When the EIA-485 shield is in full conduit:
communicate with the LED-10(s). The shield for the EIA-485 loop must be con-
nected to earth ground at the FACP, but must be left floating (no connection) at the
LED-10 if it is the first or only device on the EIA-485 loop. If a second LED-10 is
connected, the shield leaving the first LED-10 must be left floating. The shield
entering the second LED-10 must be connected to the Earth Ground Terminal
(TB1- 6 & 7) on the second LED-10. If additional LED-10s are connected, the
shield leaving each LED-10 must be left floating and the shield entering the
following unit must be connected to the Earth Ground Terminal (TB1 - 6 & 7) on the
LED-10.
Caution! Do not allow the floating (no connection) end of the shield to contact the
conduit. The floating end should be insulated from earth ground.
LED-10 Box
LED-10 Box
LED-10 Box
LED-10 Box
LED-10 Box
Notes:
Notes:
Notes:
Notes:
Notes:
1) Power-limited 24 VDC regulated power may be run in the same conduit as the EIA-485 wiring.
2) Twisted, shielded wire is recommended for the EIA-485 communications loop.
3) Each LED-10 electrical backbox is connected to earth ground via the conduit.
4) Shield is connected to the FACP cabinet (earth ground) leaving the FACP.
Technical Manuals Online! - http://www.tech-man.com
Connect the shield drain wire to the
Earth Ground Terminal on the LED-10.
Shield Drain Wire
Document 50400
firealarmresources.com
Rev A
5/15/96
P/N 50400:A
LED-10
LED-10
LED-10
LED-10
LED-10
TB2-1 (+) EIA-485
TB2-1 (+) EIA-485
TB2-1 (+) EIA-485
TB2-1 (+) EIA-485
TB2-1 (+) EIA-485
TB2-2 (-) EIA-485
TB2-2 (-) EIA-485
TB2-2 (-) EIA-485
TB2-2 (-) EIA-485
TB2-2 (-) EIA-485
TB1-6 Earth Ground
TB1-6 Earth Ground
TB1-6 Earth Ground
TB1-6 Earth Ground
TB1-6 Earth Ground
(IN)
(IN)
(IN)
(IN)
(IN)
19