The EIA-485 circuit must be wired using a twisted-shielded pair cable having a charac-
teristic impedance of 120 ohms, +/- 20%. Do not run cable adjacent to, or in the same
conduit as, 120-volt AC service, noisy electrical circuits that are powering mechanical
bells or horns, audio circuits above 25 V
Note:
Note:
Note: To ensure static (ESD - electrostatic discharge) protection, all enclosures,
Note:
Note:
including the LED-10 electrical box, must be connected to earth ground! Never use the
EIA-485 shield for this purpose. The EIA-485 shield is for radiated noise emission
protection (RFI, EMI). Refer to the following figures.
The EIA-485 shield should be terminated as follows:

When the EIA-485 shield is not in conduit:

When the EIA-485 shield is not in conduit:
When the EIA-485 shield is not in conduit:
When the EIA-485 shield is not in conduit:
When the EIA-485 shield is not in conduit: The EIA-485 loop allows the FACP to
communicate with the LED-10(s). The shield for the EIA-485 loop must be con-
nected to earth ground at the FACP but must be left floating (no connection) at the
LED-10 if it is the first or only device on the EIA-485 loop. If a second LED-10 is
connected, the shield leaving the first LED-10 must be left floating. The shield
entering the second LED-10 must be connected to the 3-gang box or Earth Ground
terminal (TB1-6 & 7) on the second LED-10. If additional LED-10s are connected,
the shield leaving each enclosure must be left floating and the shield entering each
must be connected to the 3-gang box or the Earth Ground Terminal (TB1-6 & 7) on
the LED-10.
Connect the drain wire to the
outside of the MS-5210UD cabinet
via a BX-type connector.
Shield Drain Wire
18
18
18
18
18
Technical Manuals Online! - http://www.tech-man.com
EIA-485 Shield T T T T T er er er er erminations
EIA-485 Shield
EIA-485 Shield
EIA-485 Shield
RMS
FACP Backbox
FACP Backbox
FACP Backbox
FACP Backbox
FACP Backbox
Document 50400
firealarmresources.com
minations
minations
minations
minations
, motor control circuits, or SCR power circuits
Rev A
5/15/96
P/N 50400:A
(+) EIA-485
(+) EIA-485
(+) EIA-485
(+) EIA-485
(+) EIA-485
(-) EIA-485
(-) EIA-485
(-) EIA-485
(-) EIA-485
(-) EIA-485
FACP
FACP
FACP
FACP
FACP

Advertisement

Table of Contents
loading

Table of Contents