Figure 3-3, Automatic 4-Stage Charging Graph - Magnum Energy ME3112-U Owner's Manual

Modifi ed sine wave inverter/chargers
Table of Contents

Advertisement

The Charge mode provides up to four separate charging stages: Bulk Charging, Absorb Charging,
Float Charging, and Full Charge (see Figure 3-3).
Bulk Charging: This is the initial stage of charging. While bulk charging, the charger supplies
the battery with constant current. The charger will remain in bulk charge until the absorption
charge voltage (determined by the Battery Type selection*) is achieved. The inverter's green
LED stays ON (solid) to indicate bulk charging.
Absorb Charging: This is the second charging stage and begins after the absorb voltage has
been reached. Absorb charging provides the batteries with a constant voltage and reduces
the DC charging current in order to maintain the absorb voltage setting. The inverter's green
LED fl ashes once every second (medium fl ash) to indicate absorption charging for 2 hours
(determined by the Battery AmpHrs selection*), then switches to fl oat charging.
Float Charging: The third charging stage occurs at the end of the absorb charging time.
While fl oat charging, the charge voltage is reduced to the fl oat charge voltage (determined by
the Battery Type selection*). In this stage, the batteries are kept fully charged and ready if
needed by the inverter. The inverter's green LED fl ashes once every 8 seconds (slow fl ash) to
indicate fl oat charging. The Float Charging stage reduces battery gassing, minimizes watering
requirements (for fl ooded batteries), and ensures the batteries are maintained at optimum
capacity.
Full Charge (Battery Saver™ mode): The fourth stage occurs after four hours in the Float
Charging stage. The Full Charge stage is designed to keep batteries fully charged over long
periods and prevent excessive loss of water in fl ooded batteries, or drying out of GEL/AGM
batteries. In this stage, the charger is turned off and begins monitoring the battery voltage;
if the battery voltage drops low (<12.7 VDC), the charger automatically initiates another four
hours in fl oat charge.
Info: If the battery voltage falls to the re-bulk voltage (≤12.1 VDC), the unit will begin
another bulk charge.
* These settings in the ME Series are changeable and leave the factory with default values (see Table
3-2, Inverter/Charger Default Values). These default values are adequate for most installations, however,
if you determine that some of the values need to be changed for your particular system, a remote
control may be purchased to adjust these settings.
DC
Voltage
Time
DC
Current

Figure 3-3, Automatic 4-Stage Charging Graph

© 2017 Sensata Technologies
Bulk
Charging
Increased
Voltage
Max
Charge
Rate
Constant
Current
Absorb
Charging
Charging
Absorb
volts
Constant
Reduced
Voltage
Voltage
Absorb
Time
Monitored
Reduced
Current
Current
Operation
Float
Full
Charge
Float
volts
Monitored
Voltage
Goes to Full
Charge after
4 hours in
Float Charge
No Current
Page 33