2.5.8
AC Wiring Confi guration (MS2000 models)
The following table provides the diff erent wiring confi gurations for installing and connecting the
AC conductors to and from MS2000 model inverters (see Figures 2-16 and 2-17 for installation
diagrams showing these confi gurations).
Table 2-4, AC Input/Output Wiring Confi gurations (MS2000 models)
AC Source
Required
Reason to
Appropriate
Models
Maximum
Input
Breaker
Required
Minimum
Wire Size
Maximum
Inverter
Pass-thru
capacity
Wiring
Diagram
Note
– AC source is from either the utlity/grid power (i.e., shorepower) or an AC generator.
1
© 2016 Sensata Technologies
SI/SO (30A)
Single In/Single
Out (30A)
120 VAC @ ≤30
1
amps
Have an 120 VAC
Use
source that is ≤30
amps.
Requires a
separate inverter
sub-panel.
MS2000
30A
(single pole)
–
–
#10 AWG
(In & Out)
3600W
(30A @ 120 VAC)
Figure 2-16
SI/DO
Single In/
Dual Out
120 VAC @
≤30 amps
@ ≤15 amps per leg
(-15B models); or ≤20
amps per leg
(-20B models).
Do not want to install a
separate inverter sub-
panel.
Inverter pass-thru
capability limited by
model used.
MS2000-15B
MS2000-20B
-15B models:
30A (single pole);
-20B models:
30A (single pole)
–
#10 AWG (In) -20B
models: #12 AWG x2
(Out)
-15B models: #14 AWG
x2 (Out)
-15B models: 15A/leg
(30A max.);
-20B models: 20A/leg
(30A max.)
Figure 2-17
Installation
Page 32