Ac Wiring Confi Guration (Ms2000 Models); Table 2-4, Ac Input/Output Wiring Confi Gurations (Ms2000 Models) - Sensata Magnum Energy MS Series Owner's Manual

Pure sine wave inverter/charger
Table of Contents

Advertisement

2.5.8
AC Wiring Confi guration (MS2000 models)
The following table provides the diff erent wiring confi gurations for installing and connecting the
AC conductors to and from MS2000 model inverters (see Figures 2-16 and 2-17 for installation
diagrams showing these confi gurations).
Table 2-4, AC Input/Output Wiring Confi gurations (MS2000 models)
AC Source
Required
Reason to
Appropriate
Models
Maximum
Input
Breaker
Required
Minimum
Wire Size
Maximum
Inverter
Pass-thru
capacity
Wiring
Diagram
Note
– AC source is from either the utlity/grid power (i.e., shorepower) or an AC generator.
1
© 2016 Sensata Technologies
SI/SO (30A)
Single In/Single
Out (30A)
120 VAC @ ≤30
1
amps
Have an 120 VAC
Use
source that is ≤30
amps.
Requires a
separate inverter
sub-panel.
MS2000
30A
(single pole)
#10 AWG
(In & Out)
3600W
(30A @ 120 VAC)
Figure 2-16
SI/DO
Single In/
Dual Out
120 VAC @
≤30 amps
@ ≤15 amps per leg
(-15B models); or ≤20
amps per leg
(-20B models).
Do not want to install a
separate inverter sub-
panel.
Inverter pass-thru
capability limited by
model used.
MS2000-15B
MS2000-20B
-15B models:
30A (single pole);
-20B models:
30A (single pole)
#10 AWG (In) -20B
models: #12 AWG x2
(Out)
-15B models: #14 AWG
x2 (Out)
-15B models: 15A/leg
(30A max.);
-20B models: 20A/leg
(30A max.)
Figure 2-17
Installation
Page 32