Frequency Source Setting (A001); Run Command Source Setting (A002, C001 To C008, C019, F004) - Hitachi SJ700-4000HFU2 Instruction Manual

Hide thumbs Also See for SJ700-4000HFU2:
Table of Contents

Advertisement

Chapter 4
4.2.4 Frequency source setting
The frequency source setting function allows you to select the method to
input the frequency-setting command.
Motor rotation direction is inverted when -10 to 0V is given as frequency command to 02-L terminals.
Item
Function code
Frequency
source
A001
setting
4.2.5 Run command source setting
The run command source setting function allows you to select the
method to input operation commands (to start and stop the motor).
As the operation commands via control circuit terminals, turn the FW
signal (for forward operation) or RV signal (for reverse operation) on and
off to start and stop the motor, respectively.
(Note that the factory setting assigns the FW signal to intelligent input terminal [8].)
To switch each intelligent input terminal between a and b contacts, specify each terminal with function "C011" to
"C019", and then perform input a/b (NO/NC) selection for each terminal.
When using the digital operation for the inverter operation, specify the desired motor operation direction with
function "F004", and use the RUN and STOP/RESET keys to start and stop the motor, respectively.
If the start commands for both forward and reverse operations are input at the same time, the inverter will assume
the input of a stop command.
Item
Function code
Run command
source setting
Terminal [FW]
active state
C011 to C018
Note 1: If function "31" (forcible operation) or "51" (forcible-operation terminal) is assigned to an intelligent input terminal, the
settings made with functions "A001" and "A002" will be invalidated when the said intelligent input terminal is turned on
and those methods to input frequency-setting and operation commands which are specified for the said terminal will be
enabled.
Note 2: On the remote operator (SRW) being used to operate the inverter, pressing the REMT (remote) key enables you to input
both frequency-setting and operation commands from the remote operator.
Note3: When the DeviceNet option board (SJ-DN) is used, A002 is not needed to be changed from default because the run
command source is automatically set via DeviceNet. (In case it is changed, it is to be set as 01, 02 or 03.)
Data
(Valid only when the OPE-SR is used)
(00)
Use the control provided on the digital operator to set the frequency.
Input the frequency-setting command via a control circuit terminal (0-L, OI-L,
01
or O2-L).
Use the digital operator (function "F001") or remote operator to set the
02
frequency.
03
Input the frequency-setting command via an RS485 communication terminal.
Input the frequency-setting command from the board connected to optional
04
port 1.
Input the frequency-setting command from the board connected to optional
05
port 2.
Use the SJ-FB to input the frequency-setting command as a pulse train
06
(see 4.2.21)
Use the SET-Freq command of the easy sequence function as the
07
frequency-setting command.
Use the operation result of the set frequency operation function as the
10
frequency-setting command. (see 4.2.12)
Data
01
02
A002
03
04
05
C019
00
01
Explanation of Functions
Description
A002: Run command source setting
C001 to C008: Terminal [1] to [8] functions
C019: Terminal [FW] active state
F004: Keypad Run key routing
Description
Input the start and stop commands via control circuit terminals
(FW and RV).
Input the start and stop commands from the digital or remote
operator.
Input the start and stop commands via RS485 communication
terminals.
Input the start and stop commands from option board 1.
Input the start and stop commands from option board 2.
a (NO) contact
b (NC) contact
4-8
Related code
A001: Frequency source setting
Related code

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sj700d-3 series

Table of Contents