Am And Ami Terminals (C028, C029, C106, C108 To C110) - Hitachi SJ700-4000HFU2 Instruction Manual

Hide thumbs Also See for SJ700-4000HFU2:
Table of Contents

Advertisement

Chapter 4
4.2.82 AM and AMI terminals
You can monitor the inverter output frequency and output current via the AM and
AMI terminals on the control circuit block.
The AM terminal outputs an analog voltage signal (0 to 10 V).
The AMI terminal outputs an analog current signal (4 to 20 mA).
The early precision is +-20%. Please adjust it as needed.
(1) AM siginal selection /AMI signal selection
Select the signals to be output from the AM and AMI terminals among those shown below.
Item
Function code
[AM] siginal
selection /
C028/C029
[AMI] siginal
selection
*1 This signal is output only when the V/F characteristic curve selection
(see Section 4.2.18) is the sensorless vector control, 0Hz-range
sensorless vector control, or vector control with sensor.
*2 The voltage range is 0 to +10V(positive-going only),regardless of
forward or reverse moter rotation. In addition, please do offset
adjustment when this outputs negative-going of the output torque (signed).
*3 The actually detected output frequency is output when the V/F
characteristic curve selection is the vector control with sensor (A044 = 05).
*4
For detail of the function, refer "Programing software EZ-SQ user manual".
(2) AM/AMI adjustment
The early precision is +-20%. Please adjust it as needed.
Adjust the inverter output gain for the external meters connected to the AM and AMI terminals.
Item
AM gain adjustment
AM offset adjustment
AMI gain adjustment
AMI offset adjustment
*1 When the current range of AMI terminal output is 4 to 20 mA, the offset of 4 mA is approximately 20%.
The adjustment is the following procedure. (In the case of AMI, it is similar)
a.
In a state of C028=00, and please run moter at the maximum frequency.
b. Adjust offset C109 first, and then use C106 to set the voltage for full scale output.
AM output offset adjustment
AM output
C109=0~100
10V
Parallel
0
Note: In the case of use, please do the setting that had room not to be able to shake off a meter across the rating
either in C028=01,02,04.
Data
Description
00
Output frequency (*3)
01
Output current
02
Output torque (*1)
04
Output voltage
05
Input power
06
Electronic thermal overload
07
LAD frequency
09
Motor temperature
10
Heat sink temperature
11
Output torque (signed) (*1) (*2)
13
General analog YA (1) (*4)
14
General analog YA (2) (*4)
Function code
C106
C109
C107
C110
movement
Full scale (FS)
Explanation of Functions
0 to maximum frequency (Hz)
0 to Rated Output current ×2.0
0 to Rated Output torque ×2.0
0 to Rated Output voltage ×1.33
(75% of full scale is equivalent to 100%)
0 to Rated Input power ×2.0
0 to 100%
0 to maximum frequency (Hz)
0ºC to 200ºC (0ºC is output when the motor
temperature is 0ºC or less.)
0ºC to 200ºC (0ºC is output when the motor
temperature is 0ºC or less.)
(Output only from the AM terminal)
0 to Rated Output torque ×2.0
(Output only from the AM terminal)
0 to 100%
(Output only from the AMI terminal)
0 to 100%
Range of data
50. to 200. (%)
Setting of the gain for AM monitoring
0 to 100 (%)
Setting of the offset for AM monitoring
50. to 200. (%)
Setting of the gain for AMI monitoring
0 to 100 (%)(*1)
Setting of the offset for AMI monitoring
AM output gain adjustment
AM output
high number
10V
0
Full scale (FS)
4-74
Related code
C028: [AM] siginal selection
C029: [AMI] siginal selection
C106: AM gain adjustment
C109: AM offset adjustment
C108: AMI gain adjustment
C110: AMI offset adjustment
Full-scale value
(*2)
AM output
(C106)=200%
10
(V)
(C106)=100%
(C109)=50%
5
torque (%)
100
200
0
Description
C106=50.~200.
low number

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sj700d-3 series

Table of Contents