Initialization Setting (B084, B085) - Hitachi SJ700-4000HFU2 Instruction Manual

Hide thumbs Also See for SJ700-4000HFU2:
Table of Contents

Advertisement

Chapter 4
4.2.83 Initialization setting
The initialization function allows you to initialize the adjusted settings on the
inverter to restore the factory settings. You can also clear the trip history data
alone.
The settings of initialization are described below. Running-time data and power-on time data cannot be cleared.
Item
Initialization mode
(parameters or trip
history)
Country code for
initialization
(Initializing procedure)
Adjust the above settings as required, and then perform the following procedure:
RUN
PRG
RUN
STOP/
RESET
1
2
FUNC
1) Set b180=01 and press the STR.
Or
Holding down the FUNC and [2]
(down) keys, press and hold down the
STOP/RESET key.
- After the monitor starts blinking,
release only the STOP/RESET key.
(The display on the monitor changes
to that shown in the middle figure
above.
- Release the FUNC and [2] (down)
keys.
Initialization-in-progress display
intended for Europe
Initialization-in-progress display
intended for the U.S.A.
Initialization-in-progress display for
trip history clearance
Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121, C122, and
C123) and thermistor coefficient setting (C085).
Note 2: The initialization operation does not initialize the settings of easy sequence user parameters (P100 to P131).
Function code
b084
b085
POWER
ALARM
Hz
RUN
V
kW
A
PRG
%
RUN
FUNC
STR
2) Initialization is in progress.
- The above figure shows the monitor
display (indicating that the
initialization is in progress) intended
for Japan. Those intended for other
regions and trip history clearance are
shown below.
In the far-left digit, the lighting
segments move round for about
2 seconds.
Explanation of Functions
Data
00
Disabled
01
Clearing on the trip history data
Initializing only the settings
02
The factory settings are restored.
Clearing the trip history data and initializing the
03
settings
Clearing the trip history data and initializing the
04
settings and EzSQ program
00
Defaults intended for Japan
01
Defaults intended for Europe
02
Defaults intended for the U.S.A.
POWER
ALARM
Hz
V
kW
A
%
STOP/
RESET
1
2
STR
4-75
Related code
b084: Initialization mode (parameters or
trip history)
b085: Country code for initialization
Description
RUN
PRG
RUN
STOP/
RESET
1
2
FUNC
STR
3) When the initialization is completed,
the monitor displays data "0.00".
(In case of b038 = 001)
Confirm that the settings have been
initialized.
POWER
ALARM
Hz
V
kW
A
%