1106H
AT Control
1107H
Remote Input Reverse Setting
1108H
Alarm 1 Function Selection
1109H
Alarm 2 Function Selection
110AH
Alarm 3 Function Selection
110BH
Alarm 1 Output Delay Time
110CH
Alarm 2 Output Delay Time
110DH
Alarm 3 Output Delay Time
110EH
Upper Limit of Control Output 1
110FH
Lower Limit of Control Output 1
1110H
Upper Limit of Control Output 2
1111H
Lower Limit of Control Output 2
Programmable Waiting
1112H
Temeprature
1113H
Programmable Waiting Time
1114H
Programmable Slope Increase
1115H
Testing Mode
Adjust Upper Limit of Analog
1116H
Linear Output 1
Adjust Lower Limit of Analog
1117H
Linear Output 1
Adjust Upper Limit of Analog
1118H
Linear Output 2
Adjust Lower Limit of Analog
1119H
Linear Output 2
Adjust Retransmission Upper
111AH
Limit
Adjust Retransmission Lower
111BH
Limit
111CH
Event 1 Selection
111DH
Event 2 Selection
111EH
Event 3 Selection
1120H
SV Control Mode Selection
1121H
Adjust Remote Compensation
1122H
Adjust Remote Gain
Positive/Negative Selection for
1123H
Remote
1124H
Switch Slope Time Unit
1125H
Cold Junction Compensation
Reserve the Programmable
1126H
Running Status when Power OFF
1127H
Fuzzy Gain
1128H
Fuzzy Dead Band
Save Programmable Settings
1129H
into Memory
1182H
CT1 Read Value
1183H
CT2 Read Value
1. Communication Transmission Format: Command Code: 03: read words, 06: write 1 word
ASCII Mode
Read Command
STX
': '
': '
ADR 1
'0'
'0'
ADR 0
'1'
'1'
CMD 1
'0'
'0'
0: AT(Auto-tune), 1: ST(Self-tune)
0: forward, 1: reverse
Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
Bit3: Peak Record, Bit2: Hold Enable, Bit1: Output Reverse, Bit0: Standby Enable
Unit: second. Setting range: 0~100sec
Unit: second. Setting range: 0~100sec
Unit: second. Setting range: 0~100sec
Range: lower limit of control output ~100%, unit is 0.1%
Range: 0~upper limit of control output, unit is 0.1%
Range: lower limit of control output~100%, unit is 0.1%
Range: 0~upper limit of control output, unit is 0.1%
Setting range: 0~1000(100.0 )
Unit: min. Setting range: 0~900
Unit: 0.1℃/min or 0.1℃/sec--- (refer to Communication Address 1124H) Setting
range: 0~1000
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1μA, Adjust voltage: 1scale=1mV
Adjust current: 1scale=1μA
Adjust current: 1scale=1μA
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
0: OFF, 1: Run/Stop, 2: Change SV value, 3: PID/Manual control, 4: Switch to
Programmable Hold mode
0: Constant, 1: Slope increase, 2: Programmable input, 3: Remote Input
Setting range: -999~999
Setting range: -999~999
0: Positive, 1: Negative
0: min, 1: sec
0: ON, 1: OFF
0: None, 1: Running status is saved and will continue by the previous status when
power ON.
Setting range: 1~10
Setting range: 0.0~PB
0:None, 1: Saves the programmable settings into memory
Unit: 0.1A
Unit: 0.1A
Read Command Response
STX
': '
': '
ADR 1
'0'
'0'
ADR 0
'1'
'1'
CMD 1
'0'
'0'
Write Command
STX
': '
': '
ADR 1
'0'
'0'
ADR 0
'1'
'1'
CMD 1
'0'
'0'
Write Command Response
STX
': '
': '
ADR 1
'0'
'0'
ADR 0
'1'
'1'
CMD 1
'0'
'0'
21