To set Retransmission to positive/negative slopes (a Retransmission board must be installed first): In 【Initial Setting Mode】 set
the
parameter, the last digit (Y) of xxxY indicates when Y=0 positive slope; when Y=1 negative slope.
To adjust the lower limit of Retransmission:
a、 Make sure the slope of Retransmission is positive.
b、 Set lower limit value larger than the display value: In 【 Initial Setting Mode】 set the value in
(PV).
c、 Input the analog value to meter, check the meter and adjust the analog input value: In 【Regulation Mode】 , enter the new value
into
. For example, if the range is 4~20mA, the new value will be 4mA.
To adjust the upper limit Retransmission:
a、 Make sure the slope of Retransmission is positive.
b、 Set upper limit value smaller than the display value: In【Initial Setting Mode】set the value in
value (PV).
d、 Input the analog value to meter,check the meter and adjust the analog input value: In 【Regulation Mode】 , enter the new value
into
. For example, if the range is 4~20mA, the new value will be 4mA.
 Check the Firmware Version and Output Type
When the temperature controller is ON, the PV and SV display will shows firmware version, output type and accessory functions in first 3
seconds.
PV (first 3 digits) indicates the firmware version. Ex: 110 indicates firmware version V1.10.
th
PV (4
digit) indicates the function of accessory 1.
C: RS485 Communication
SV (frist 2 digits) indicates the output type of OUT1 and OUT2.
N: No function
V: Voltage pulse output
L: Linear voltage output
rd
SV (3
digit) indicates the function of accessory 2.
N: No function
C: CT measure
th
SV (4
digit) indicates the function of accessory 3.
N: No function
C: CT measure
 Selection for Heating/Cooling/Alarm/Dual Loop Output Control
CND3 series offers 1 set of Output Control (OUT1) that is built-in internally and 2 sets of Alarm Output(ALARM1 and ALARM2). User
nd
can also purchase a 2
set of Output Control (OUT2) or a 3
Using 1 set of Output Control :
In【Initial Setting Mode】, sets
nd
Using 2
set of Output Control:
nd
When the 2
set of output control (OUT2) is used as a 3
Cooling + Alarm 3(C1A2) in 【Initial Setting Mode】.
OUT2 output types in relay, voltage pulse, analog current, linear voltage and SSR output can all be used for ALARM ON-OFF. For
example, OUT2 is set to analog current output. It outputs 4mA when alarm is OFF and outputs 20mA when alarm is ON.
nd
When the 2
set of output control (OUT2) is used as dual output control, set
Heating/Cooling(H1C2) or Cooling/Heating (C1H2) control mode in【Initial Setting Mode】.
The Dead Band parameter
in the diagram follow. The purpose of Dead Band function is to reduce the energy wastage of frequent heating/cooling actions. For
example, if SV = 100 degree and
Output of
when in ON-OFF control mode (Ctrl=ON-OFF control):
Adjust heating hysteresis
Heating
E: EVENT3 Input
R: Relay output
S: SSR output
E: EVENT1 input
E: EVENT2 input
rd
set of Alarm Output (ALARM3).
to Heating (H1) or Cooling(C1) mode.
is automatically enabled when the temperature controller is in dual output control. As shown
= 2.0, there will be no output when the temperature is between 99~101°C..
Adjust cooling hysteresis
Cooling
Set Point
C: Current output
R: REMOTE input
R: RETRANSMISSION output
rd
set of arlarm (ALARM3), set
larger than the display value
smaller than the display
to Heating + Alarm 3(H1A2) or
to heating (H1H2); cooling (C1C2);
9