Download Print this page

Omega CND3 Series User Manual page 13

Hide thumbs Also See for CND3 Series:

Advertisement

the start status, the program will start running from the initial pattern and initial step.
When setting control is in pause control and temperature is controlled at the setting value before the stop, by re-selecting
the start status, the program will start running from the step where the program was paused and carry out the remaining
part.
Set parameter
Set initial pattern: Set parameter
Set initial step: Set parameter
Select edit pattern: Set parameter
Press
"SP'x'F", "tM'x'F", "PSY'x' ", "CYC'x' ", "LiN'x' ", where 'x' is the selected pattern, which can be 0, 1, ..., E,
F. "SP'x'0"、 "SP'x'1"、..."SP'x'F" are temperature settings of this step; " tM'x'0" 、" tM'x'1"、 ... " tM'x'F" are time
settings of this step; "PSY'x' " is the maximum effective procedure; "CYC'x' " is the number of loops for executing
the loop, "LiN'x'" is the number of the subsequent patterns to be linked after executing this pattern.
Set initial slope: Set initial slope by parameter
Set wait temperature: Set wait temperature by parameter
Set wait time: Unit min., set wait time by parameter
Set unit of program edit time: Set value corresponding to Y position of parameter
xxYx (Y is 0 or 1; 0:℃/min., 1:℃/s)
Set SV display method on program mode: Set value corresponding to Y position of parameter
Mode】, e.g., Yxxx (Y is 0 or 1; 0:normal, 1:dynamic)
Set power off saving on program mode: Set value corresponding to Y position of parameter
Mode】, e.g., xxxY (Y is 0 or 1; 0:normal., 1:power off saving)
Note: When any settings or changes of the program parameters are made, please save the settings/changes to the
controller by opting for parameter SAVE. Otherwise, the settings/changes will be reset upon power-off.
How to SAVE:
Select
key is displayed only when any settings/changes are made.
Using RS485 communicatiion writing value 1 to address 1129H, the parameters will be saved.
Remote Mode: Input of setting value can be dynamic, an analog value (voltage or current) can be converted into a dynamic input
value. Two methods can be used for the conversion: positive slope or negative slope, they are depicted as follows:
a、 Positive slope Remote setting: Display of Remote analog input is in positive proportion with setting input, e.g.: Remote input
type is selected as 1~5 V analog voltage, Remote higher limit of input is set as 5000, Remote lower limit of input is 1000,
decimal display is set as 0; when Remote input is 5V, the screen shows 5000; when Remote input is 2V, the screen show
2000; this is the dynamic setting of the screen display. (Dynamic setting value =(Remote higher limit of input – Remote lower
limit of input)*(Remote input value - lower limit of Remote input)/( higher limit of Remote input - lower limit of Remote input)+
Remote lower limit of input)
b、 Negative Slope Remote setting: Display of Remote analog input is in negative proportion with setting input, e.g.: Remote
input type is selected as 1~5 V analog voltage, Remote higher limit of input is set as 5000, Remote lower limit of input is 1000,
decimal display is set as 0; when Remote input is 5V, the screen shows 1000; when Remote input is 2V, the screen show
4000; this is the dynamic setting of the screen display. (Dynamic setting value =(Remote higher limit of input – Remote lower
to
In 【Initial Setting Mode】
to initial pattern in 【Operation Mode】.
to initial step in【Operation Mode】
in 【Initial Setting Mode】 to set the pre-edit pattern, assume selection is 'x'.
key
to
select
the
in the menu, then press the
patterns
including
"SP'x'0",
in 【Initial Setting Mode】(unit: 0.1℃/min. or 0.1℃/s)
in 【Initial Setting Mode】.
in 【Initial Setting Mode】.
keys and select
"tM'x'0",
"SP'x'1",
"tM'x'1"...
in 【Initial Setting Mode】, e.g.,
in 【Initial Setting
in 【Initial Setting
to complete saving. The
11

Advertisement

loading

This manual is also suitable for:

Cn16d3-r-ac