Omega CND3 Series User Manual page 22

Hide thumbs Also See for CND3 Series:

Advertisement

2nd output group
Output value read and write of
1012H
Output 1
Output value read and write of
1013H
Output 2
1016H
Temperature regulation value
1017H
Analog decimal setting
101CH
PID parameter selection
SV value corresponded to PID
101DH
value
1020H
Alarm 1 type
1021H
Alarm 2 type
1022H
Alarm 3 type
1024H
Upper-limit alarm 1
1025H
Lower-limit alarm 1
1026H
Upper-limit alarm 2
1027H
Lower-limit alarm 2
1028H
Upper-limit alarm 3
1029H
Lower-limit alarm 3
102AH
Read LED Status
102BH
Read Pushbutton Status
102CH
Setting lock status
102FH
Software version
1030H
Start pattern number
Remaining time of the executed
1032H
step (second)
Remaining time of the executed
1033H
step (minute)
1034H
No. of currently executed step
1035H
No. of currently executed pattern
Read dynamic value in
1036H
programmable control
1039H
Communication write
Temperature unit display
103AH
selection
103BH
AT setting
103CH
Control RUN/STOP setting
101FH
Start step number
Pattern 0~15 temperature set
point setting (Even number)
1200H~13FFH
Pattern 0~15 execution time
setting (Odd number)
Actual number of step setting
1400H~140FH
inside the corresponding pattern
Cycle number for repeating the
1410H~141FH
execution
pattern
Link pattern number setting of
1420H~142FH
the correspond pattern
Address
1100H
Adjust Temperature Gain
1101H
Temperature Filter Range
1102H
Temperature Filter Factor
1103H
Reverse Output
1104H
Slope of Temperature Increase
1105H
Remote Input Type Selection
Unit is 0.1%, write operation is valid under manual tuning mode only.
Unit is 0.1%, write operation is valid under manual tuning mode only.
-99.9 ~ +99.9. Unit is 0.1
0 ~ 3
0~5/AUTO
Only valid within available range, unit: 0.1 scale
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
b0: ALM3, b1: ALM2, b2: ℃, b3: ℉, b4: ALM1, b5: OUT2, b6:OUT1, b7: AT
b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key
V1.00 indicates 0x100
0 ~ 15
Only read
Only read
Only read
Only read
Only read
0: Disable (default), 1: Enable
0:
0: OFF (default), 1: ON
0: STOP, 1: RUN (default), 2:END (program mode), 3: HOLD (program mode)
0 ~ 15
-999 ~ 9999
Time: 0 ~ 900(1 minute per scale)
0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N
of
the
correspond
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the
program end and execution end. 0~15 indicates the next execution pattern
number after executing the current pattern
Content
Range of temperature filter: 10~1000, unit: 0.01 ℃, default: 100(1.0℃)
Setting range: 0~50, default: 8
Bit1: output 2, Bit0: output 1
Unit: 0.1 /
0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V
, 1:
℃ linear input (default)
/
℃ min or 0.1℃/sec (refer to CommunicationAddress 1124H)
Definition
20

Advertisement

loading

This manual is also suitable for:

Cn16d3-r-ac