Underwriter's Labs Inc. (ULI) United States 2-Wire Smoke Detector
Control Panel Compatibility
Notes:
• Reset time, hold for five seconds minimum.
• Whether mixing different models of compatible smoke detectors, or using the same
model on the same circuit, total standby current of all detectors must not exceed 3
mA.
• The below-listed smoke detectors are compatible with initiating circuits having
Compatibility Identifier "A".
Smoke
Compatibility
Detector
Identifier
Make Model /
Head / Base
Base
System Sensor
1100
A - N/A
1151/
A - A
B110LP
1151/
A - A
B116LP
1400
A - N/A
1451/B401
A - A
1451/
A - A
B401B
1451/
A - A
B406B
1451DH/
A - A
DH400
2100
A - N/A
2100T
A - N/A
2151/
A - A
B110LP
2151/
A - A
B116LP
Rated
Smoke Detector
Standby
Make Model /
Current
Base
Sentrol - ESL
0.12 mA
429C
0.12 mA
429CT
0.12 mA
429CST
0.10 mA
429CRT
711U/701E,
0.12 mA
701U, 702E,
702U
712U / 701E,
0.12 mA
701U, 702E,
702U
713-5U / 701E,
0.12 mA
701U, 702E,
702U
713-6U / 701E,
0.12 mA
701U, 702E,
702U
721U / 702E,
0.12 mA
702U
721UT / 702E,
0.12 mA
702U
722U / 702E,
0.12 mA
702U
731U / 702E,
0.12 mA
702U, 702RE,
702RU
FA-1025T Installation and Operation Manual
Compatibility
Rated Standby
Identifier Head /
Current
Base
S10A - N/A
0.10 mA
S10A - N/A
0.10 mA
S11A - N/A
0.10 mA
S11A - N/A
0.10 mA
S10A - S00
0.10 mA
S10A - S00
0.10 mA
S10A - S00
0.10 mA
S10A - S00
0.10 mA
S10A - S00
0.10 mA
S10A - S00
0.10 mA
S10A - S00
0.10 mA
S11A - S00
0.10 mA