Figure 4.7 - Wire Routing Locations For 200-400 Hp Drives - Reliance electric 2V4160 Hardware Installation And Troubleshooting Manual

Ac drive
Table of Contents

Advertisement

POWER CONNECTIONS
PULL SHIELD TABS IN AND ROTATE SHIELD OUT
CONNECT USING 350MCM TWO HOLE TERMINAL LUGS
TORQUE TO 325IN-LBS
GND
DC-
DC+
-DC
DANGER
D-C BUS CAPACITORS RETAIN HAZARDOUS VOLTAGES
AFTER INPUT POWER HAS BEEN DISCONNECTED.
WAIT FIVE (5) MINUTES FOR THE D-C BUS
CAPACITORS TO DISCHARGE AND THEN CHECK THE
VOLTAGE WITH A VOLTMETER THROUGH THE ACCESS
SLOTS SHOWN ABOVE. VOLTAGE MUST BE 50 VOLTS
OR LESS PRIOR TO SERVICING.
BM
ALLOW 6 INCH RADIUS SERVICE LOOP
WITH INTERCONNECTION WIRING FROM
CONTROL BOARD WIRING TRAY TO
J1 CONNECTOR ON REGULATOR BOARD.
Mounting the Drive, Grounding, and Finding Wire Routing Locations
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
GROUND, A-C INPUT AND A-C OUTPUT TERMINALS
U
V
W
R
S
T
+DC
VOLTMETER TEST POINTS
!
DANGER
1FU
CLASS CC
LITTLEFUSE
TYPE MR
OR EQUIV.
2A
2FU
Figure 4.7 – Wire Routing Locations for 200-400 HP Drives
SIGNALS (VIA WIRING TRAY)
VIEW FROM TOP
(with Cover Removed)
GND
DC-
DC+
U/T1
SIGNALS (VIA WIRING TRAY)
WIRING HARNESS 807300-138R
V/T2
W/T3 R/L1
S/L2
T/L3
4-9