3.1.3 Verifying the Site Provides for Recommended Air Flow Clearances

Be sure there is adequate clearance for air circulation around the drive. For best air
movement, do not mount GV3000/SE drives directly above each other. Note that no
devices are to be mounted behind the drive. This area must be kept clear of all control
and power wiring. Refer to figure 3.2 for recommended air flow clearances.
OFF
200-400 HP
3-4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
10cm (4")
25cm (10")*
10cm
(4")
10 cm (4")
25 cm (10")*
1-60 HP
VIEW FROM TOP
610 mm
(24.0")
C R L U
L R U
* If adjacent to other drives
Figure 3.2 – Recommended Air Flow Clearances
10cm
(4")
10 cm (4")
2 cm (0.8")
4 cm (1.6")*
10 cm (4")
60-150 HP
GV3000/SE AC Drive Hardware Reference, Version 6.06
2 cm (0.8")
4 cm (1.6")*